SERVICING
WARNING
L
INE VOLTAGE NOW PRESENT
3. Turn ON the gas and electrical power supply and oper-
ate the furnace.
4. Measure gas manifold pressure with burners firing. Ad-
just manifold pressure using the table below.
Manifold Gas Pressure
Natural Gas
Propane Gas
The final manifold pressure must not vary more than ± 0.3 "
w.c. from the above specified pressures. Any necessary
major changes in gas flow rate should be made by changing
the size of the burner orifice.
5. To adjust the gas valve pressure regulator, remove the
regulator cap.
6. Turn the adjustment screw clockwise to increase the
pressure, or counterclockwise to decrease the pressure.
7. Securely replace the regulator cap.
HIGH VOLTAGE
D
ALL
ISCONNECT
ELECTRICAL POWER AND SHUT OFF GAS
SUPPLY BEFORE SERVICING OR INSTALLING THIS UNIT.
M
ULTIPLE POWER SOURCES MAY BE PRESENT.
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
8. Disconnect manometer after turning off gas at manual
shutoff valve. Reinstall gas valve outlet pressure tap plug
before turning on gas to furnace.
9. Turn on gas to furnace and check for leaks. If leaks are
found, repair and then reinstall burner compartment door.
10. Turn on electrical power and verify proper unit operation.
Gas Manifold Pressure Measurement and Adjust-
ment (80% & 90% Two-Stage Furnaces)
Natural Gas Adjustments
HIGH VOLTAGE
D
ALL
ISCONNECT
ELECTRICAL POWER AND SHUT OFF GAS SUPPLY
BEFORE SERVICING OR INSTALLING.
1. After turning off gas to furnace at the manual gas shutoff
valve external to the furnace, remove burner compart-
ment door to gain access to the gas valve.
3.5" w.c.
10.0" w.c.
WARNING
F
AILURE TO
WARNING
2. Connect a calibrated water manometer (or appropriate
gas pressure gauge) at the gas valve outlet pressure
tap. Refer to previous Measuring Manifold Gas Pres-
sure figure for proper connection.
WARNING
L
INE VOLTAGE NOW PRESENT
3. Turn ON the gas and electrical power supply and oper-
ate the furnace.
4. Remove the cap screw from the high stage manifold
pressure regulator.
5. Using a 3/32" Allen wrench, adjust the high stage mani-
fold pressue regulator to the required pressure setting.
6. Reinstall high stage cap screw and recheck manifold
pressure setting with cap on.
7. Remove the cap screw from the low stage manifold pres-
sure regulator.
8. Using a 3/32" Allen wrench, adjust the low stage regu-
lator to the required pressure setting.
9. Reinstall low stage cap screw and recheck manifold
pressure setting with cap on.
HIGH VOLTAGE
D
ALL
ISCONNECT
ELECTRICAL POWER AND SHUT OFF GAS SUPPLY
BEFORE SERVICING OR INSTALLING.
10. Disconnect manometer after turning off gas at manual
shutoff valve. Reinstall gas valve outlet pressure tap
plug before turning on gas to furnace.
11. Turn on gas to furnace and check for leaks. If leaks are
found, repair and then reinstall burner compartment
door.
12. Turn on electrical power and verify proper unit opera-
tion. Make sure furnace operates at the proper mani-
fold pressure at both high and low stage outputs.
Manifold Gas Pressure
Gas
Rate
High Stage 3.2 to 3.8" w.c. 3.5" w.c.
Natural Gas
Low Stage 1.6 to 2.2" w.c. 1.9" w.c.
WARNING
Range
Nominal
121