General Specifications

Item
Operating Temperature
Storage Temperature
Operating Humidity
storage Humidity
Vibration Resistance
- Direct Mounting
Vibration Resistance
- DIN rail Mounting
Shock Resistance
Noise Immunity
Dielectric Withstand
Voltage
Insulation Resistance
Ground
Certification
EC Directive
*1 Perform dielectric withstand voltage and insulation resistance tests at the stated voltage
between each terminal and the main unit's ground terminal.
0 to 55 °C (32 to 131 °F)
-20 to 70 °C (-4 to 158 °F)
35 to 85% Relative Humidity, No condensation
35 to 90% Relative Humidity, No condensation
Conforms to EN 68-2-6; 10 - 57 Hz: 0.075 mm Half Amplitude
57 - 150 Hz: 9.8 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Conforms to EN 68-2-6; 10 - 57 Hz: 0.035 mm Half Amplitude
57 -150 Hz: 4.9 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Conforms to EN 68-2-27: 147m/s
3 times in each direction X, Y, and Z
1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
AC PSU: 1500 V AC > 1 min., tested between each terminal with ground terminal
DC PSU: 500 V AC > 1 min., tested between each terminal with ground terminal
5 MΩ > at 500 V DC, tested between each terminal with ground terminal
Grounding resistance 100 Ω or less
UL/cUL (UL508)
EMC (EN61000-6-2, EN50081-2), LVD (EN61010-1)
Description
2
Acceleration
2
Acceleration
2
Acceleration, Action Time: 11 ms