MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER

12-1. HOW TO "MONITOR THE OPERATION DATA"
12-1-1. PAR-30MAA/PAR-31MAA
Details on the operation data including each thermistor temperature and error history can be confirmed with the remote controller.
Select "Service" from the Main menu, and press the
1
Select "Check" with the F1 or F2 button, and press the
Select "Request code" with the F1 or F2 button, and press the
Set the Refrigerant address and Request code.
2
Select the item to be changed with the F1 or F2 button.
Select the required setting with the F3 or F4 button.
■ <Ref.address>setting [ 0 ] – [ 15 ]
■ <Request code>setting
Press the
button, Data will be collected and displayed.
OCH582B
button.
button.
button.
Request code: 004
Discharge temperature: 69˚C
83
Check menu
Error history
Refrigerant volume check
Refrigerant leak check
Smooth maintenance
Request code
Service menu:
Cursor
F1
F2
F3
F4
Request code
Ref.address
Request code
Request:
Cursor
F1
F2
F3
F4
Request code
Ref.address
Request code
Request: