Gas Piping - Lennox SLP98DFV Installation Instructions Manual

Hide thumbs Also See for SLP98DFV:
Table of Contents

Advertisement

Gas Piping

CAUTION
If a flexible gas connector is required or allowed
by the authority that has jurisdiction, black iron
pipe shall be installed at the gas valve and extend
outside the furnace cabinet.
WARNING
Do not over torque (800 in-lbs) or under torque (350
in-lbs) when attaching the gas piping to the gas
valve.
1 - Gas piping may be routed into the unit through either
the left or right-hand side. Supply piping enters into
the gas valve from the side of the valve as shown
in figure 42. Connect the gas supply piping into the
gas valve. The maximum torque is 800 in lbs and
minimum torque is 350 in lbs when when attaching
the gas piping to the gas valve.
2 - When connecting gas supply, factors such as length
of run, number of fittings and furnace rating must
be considered to avoid excessive pressure drop.
Table 10 lists recommended pipe sizes for typical
applications.
NOTE - Use two wrenches when connecting gas piping to
avoid transferring torque to the manifold.
3 - Gas piping must not run in or through air ducts,
clothes chutes, chimneys or gas vents, dumb
waiters or elevator shafts. Center gas line through
piping hole. Gas line should not touch side of unit.
See figure 42.
4 - Piping should be sloped 1/4 inch per 15 feet (6mm
per 5.6m) upward toward the gas meter from the
furnace. The piping must be supported at proper
intervals, every 8 to 10 feet (2.44 to 3.05m), using
suitable hangers or straps. Install a drip leg in
vertical pipe runs to serve as a trap for sediment or
condensate.
5 - A 1/8" N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See figures 48.
6 - In some localities, codes may require installation of
a manual main shut-off valve and union (furnished
by installer) external to the unit. Union must be of
the ground joint type.
Compounds used on threaded joints of gas
piping must be resistant to the actions of liquified
petroleum gases.
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
1/8" N.P.T. PLUGGED TAP
Leak Check
After gas piping is completed, carefully check all piping
connections (factory- and field-installed) for gas leaks.
Use a leak detecting solution or other preferred means.
The furnace must be isolated from the gas supply system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply system at pressures
less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
I
When testing gas lines using pressures in excess of
1/2 psig (3.48 kPa), gas valve must be disconnected
and isolated. See figure 41. Gas valves can be
damaged if subjected to pressures greater than 1/2
psig (3.48 kPa).
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could
result in serious injury, death, or property damage.
Never use an open flame to test for gas leaks. Check
all connections using a commercially available
soap solution made specifically for leak detection.
Some soaps used for leak detection are corrosive
to certain metals. Carefully rinse piping thoroughly
after leak test has been completed.
Page 29
IMPORTANT
CAP
GAS VALVE
FIGURE 41
IMPORTANT
WARNING
FURNACE
ISOLATE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents