SiENBE05-722_A
3.16 Compressor System Sensor Abnormality
H0
Remote Control
Display
The system checks the DC current before the compressor starts.
Method of
Malfunction
Detection
The DC current before compressor start-up is out of the range 0.5 ~ 4.5 V (sensor output
Malfunction
Decision
The DC voltage before compressor start-up is below 50 V.
Conditions
Broken or disconnection of harness
Supposed
Defective outdoor unit PCB
Causes
Troubleshooting
Check the relay harness for the
compressor.
Turn off the power and turn it on
again.
Service Diagnosis
converted to voltage value)
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is the harness
broken?
NO
Restart operation
and error displayed again?
YES
YES
NO
Troubleshooting
Replace the harness.
No problem.
Keep on running.
Replace the outdoor unit
PCB.
(R11712)
85