Specifi Cations - Bosch Climate 5000 AA Series Installation Manual

Inverter one-two/one-three/one-four/one-five split-type air conditioner / heat pump
Hide thumbs Also See for Climate 5000 AA Series:
Table of Contents

Advertisement

8 | Bosch Climate 5000 AA Series Inverter Multi Split-Type Air Conditioner/ Heat Pump
5 Specifi cations
Number of units that can be used together
Compressor stop/start frequency
Power source voltage
Table 2
Model
Max. equivalent length for all connected
indoor units
Max. equivalent length for one indoor unit
Max. height diff erent
OU higher than IU
between indoor and
outdoor unit
OU lower than IU
Max. height diff erent between indoor units
Table 3 Refrigerant pipe requirements
When installing multiple indoor units with a single outdoor unit, ensure that the
length of the refrigerant pipe and the drop height between the indoor and outdoor
units meet the requirements illustrated in the following diagram (indoor units may be
located above or below the outdoor unit as long as they meet these height diff erence
requirements):
Outdoor unit
Figure 3
Data subject to change
Connected units
Stop time
voltage fl uctuation
voltage drop during start
interval unbalance
1 drive 2
BMS500-AAM018-1CSXXA
BMS500-AAM027-1CSXXA
98.4 ft / 30 m
82 ft / 25 m
49 ft / 15 m
49 ft / 15 m
32.8 ft / 10 m
1 drive 3
1 drive 4
BMS500-AAM036-1CSXXA
147.6 ft / 45 m
196.8 ft / 60 m
98.4 ft / 30 m
114.8 ft / 35 m
49 ft / 15 m
49 ft / 15 m
49 ft / 15 m
49 ft / 15 m
32.8 ft / 10 m
32.8 ft / 10 m
Indoor unit
Max.Height difference
Indoor unit
Installation Manual
1-5 units
3 min or more
within ±10% of rated voltage
within ±15% of rated voltage
within ±3% of rated voltage
1 drive 5
BMS500-AAM048-1CSXXA
246 ft / 75 m
114.8 ft / 35 m
49 ft / 15 m
49 ft / 15 m
32.8 ft / 10 m
≤32.8ft
(10m)
≤49ft
(15m)
01.2017 | Bosch Thermotechnology Corp.