2 0 | Bosch Climate 5000 AA Series Inverter Multi Split-Type Air Conditioner/ Heat Pump
9.2 Adding refrigerant
CAUTION:
Refrigerant charging must be performed after wiring,
vacuuming, and the leak testing.
DO NOT exceed the maximum allowable quantity of
refrigerant or overcharge the system. Doing so can damage
the unit or impact it's functioning.
Charging with unsuitable substances may cause explosions or
accidents. Ensure that the appropriate refrigerant is used.
Refrigerant containers must be opened slowly. Always use
protective gear when charging the system.
DO NOT mix refrigerants types.
N=2(one-twin models), N=3(one-three models), N=4(one-four models), N=5(one-
fi ve models).
Depending on the length of connective piping or the pressure of the evacuated
system, you made need to add refrigerant. Refer to table below for refrigerant
amounts to be added:
Additional refrigerant per pipe length
Connective Pipe
Pre-charge pipe length(ft/m)
Vacuum Pump
(Standard pipe lengthxN)
More than (Standard
Vacuum Pump
pipe lengthxN)ft/m
Table 10
The standard pipe length is 7.5m (24.6').
Data subject to change
Air Purging
Liquid Side: Ø 6.35 (ø 0.25")
(Total pipe length - standard pipe lengthxN) x 15g/m
(Total pipe length - standard pipe lengthxN) x 0.16oZ/ft
Additional Refrigerant
N/A
Liquid Side: Ø 9.52 (ø 0.375")
(Total pipe length - standard pipe lengthxN) x 30g/m
(Total pipe length - standard pipe lengthxN)x 0.32oZ/ft
01.2017 | Bosch Thermotechnology Corp.
Installation Manual