Cooling Components - Siemens Simodrive 611 Configuration Manual

Drive converters
Hide thumbs Also See for Simodrive 611:
Table of Contents

Advertisement

02.12
05.01
2.7.1

Cooling components

Depending on the cooling method used, additional fan units and fan compo-
nents, specifically designed for the system, must also be ordered.
A differentiation is made between three different cooling types.
1. For internal cooling, the complete power loss remains in the electrical cabi-
2. With external cooling, the power module power loss (thermal) is externally
3. For pipe cooling, version with 300 mm wide modules with internal cooling,
The mounted fan is connected directly to the control cabinet line supply.
Fig. 2-6
Standard system design for 300 mm wide modules with mounted fan for internal cooling
Warning
!
The fan may only be commissioned if it is electrically connected to the module
housing (PE fan via module housing).
Caution
!
If the fan has an incorrect direction of rotation (see arrow) then cooling is not
guaranteed!
© Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
net in the form of heat.
dissipated in the form of heat and the power loss of the control unit is inter-
nally dissipated in the form of heat.
the complete power loss in the form of heat is conducted to the outside us-
ing a pipe connected to the module.
2 System Configuration
2.7 Infeed modules
2-57