Installation Of Single Xl19I Unit Under A Deck - Trane XL19i-APG02-EN Application Manual

Table of Contents

Advertisement

A. Installation of single XL19i unit under a deck.
1. Single XL19i units may be installed under a deck provinding the following criteria is met:
a) 3 feet minimum top clearance is provided.
b) 3 feet away from obstructions such as a wall, or shrubbery on two sides.
c) The other two sides left unobstructed.
d) Decking material overhanging the unit not to exceed two feet on two sides.
e) Servicability - Adequate space provided for annual service and maintenance. National Electric
Code (NEC) requires minimum 3 feet service clearance for personnel safety. This distance may be
increased under certain conditions. Please refer to the most current edition of the National Electric
Code for more information. Page 15 of this document contains some NEC information.
f) Condensing unit shall be set on firm foundation independent from building strucutre, not directly
on ground surface. (Photo below for illustration purposes only)
g) Consult with local building department to assure the installation will comply with local code
before installing the equipment.
Illustrations provided to designate required clearances. Trane recommendeds mounting the unit on a pad
that is independent of the structure. Reference section III.A.1.F on pg 8 of this document.
Pg. 8

Advertisement

Table of Contents
loading

Table of Contents