SECTION II - Unit Mounting:
This section describes appropriate methods for mounting and securing the XL19i. However, if these units
are to be mounted in a region where high winds are an issue, please refer to the Trane BAYECMT001
extreme conditions mounting kit. If seizmic restraint is required, please refer local code authority. This
application may require a local P.E.'s approval and stamp.
When mounting or securing the Trane condensing units and heat pumps please observe the following.
1. Anytime the unit is to be supported from the edge, the supporting material shall extend minimum two
inches under the perimeter of the unit's base.
2. The mounting hole locations are molded in the basepan, however, they must be drilled through.
a) Hole locations are identified on page 6.
b) Hole diameter is 5/16"
3. Washers should be placed in between the fastener head and the basepan.
4. Trane recommends supporting the center of the unit.
5. Base 3 and 4 pans have four mounting holes.
Refer to the dimension tables for actual unit size.
Please refer to the following illustrations for dimensions and general information.
Drawing for illustration purposes only.
Pg. 5