Step 3 - Install Machine Supports; Install Standard Isolation; Install Accessory Isolation - Carrier 19XR Installation Instructions Manual

Two-stage semi-hermetic centrifugal liquid chillers with pic 5 controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

Step 3 — Install Machine Supports
INSTALL STANDARD ISOLATION — Figures 11 and 12
show the position of support plates and shear flex pads, which
together form the standard machine support system.
IMPORTANT: Chiller housekeeping pad, anchor bolts, and
attachment points that are designed by others must be in
accordance with all applicable national and local codes.
INSTALL ACCESSORY ISOLATION (IF REQUIRED) —
Uneven floors or other considerations may dictate the use of
accessory soleplates (supplied by Carrier for field installation)
and leveling pads. Refer to Fig. 13 and 14.
Level machine by using jacking screws in isolation sole-
plates. Use a level at least 24 in. (600 mm) long.
19XR
HEAT EXCHANGER
SIZE
COOLER
CONDENSER
A4
A4
B4
A6
A6
B6
B6
C6
B8
C8
C6
C6
D6
OUTSIDE EDGE OF
COOLER TUBESHEET
(TYPICAL BOTH ENDS)
OUTSIDE EDGE OF
CONDENSER TUBESHEET
(TYPICAL BOTH ENDS)
OPTIONAL
SOLEPLATE
A
B
ft-in.
mm
ft-in.
14- 8
7
/
4492 10- 0
1
/
8
8
14- 8
7
/
4492 10- 5
3
/
8
8
16- 8
7
/
5102 10- 0
1
/
8
8
7
3
16 -8
/
5102 10- 5
/
8
8
16 -8
5080 11-11
18-8
5690 11-11
16 -8
5080 12- 4
1
/
2
16 -8
5080 13- 2
0'-0 1/2"
[13mm]
TYPICAL
X
X
0'-3"
[76mm]
TYPICAL
Fig. 11 — 19XR Machine Footprint
For adequate and long lasting machine support, proper
grout selection and placement is essential. Carrier recommends
that only pre-mixed, epoxy type, non-shrinking grout be used
for machine installation. Follow manufacturer's instructions in
applying grout.
1. Check machine location prints for required grout
thickness.
2. Carefully wax jacking screws for easy removal from
grout.
3. Grout must extend above the base of the soleplate and
there must be no voids in grout beneath the plates.
4. Allow grout to set and harden, per manufacturer's in-
structions, before starting machine.
5. Remove jacking screws from leveling pads after grout
has hardened.
DIMENSIONS
C
D
mm
ft-in.
mm
ft-in.
3051 0-4
7
/
113
1-10
16
3177 0-4
7
/
113
1-10
16
3051 0-4
7
/
113
1-10
16
7
3177 0-4
/
113
1-10
16
3632 0-4
102
1-10
3632 0-4
102
1-10
3662 0-4
102
1-10
4013 0-4
102
1-10
SUPPORT PLATE
L C
COOLER
L C
VESSELS
L C
CONDENSER
D
A
33
E
F
mm
ft-in.
mm
ft-in.
mm
559
1-4
406
559
1-4
406
559
1-4
406
559
1-4
406
559
1-4
406
559
1-4
406
559
1-4
406
559
1-4
406
Y
Y
E
C
G
ft-in.
mm
0-1
25
0-1
25
0-1
25
F
B
G

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents