Install Spring Isolation - Carrier 19XR Installation Instructions Manual

Two-stage semi-hermetic centrifugal liquid chillers with pic 5 controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

INSTALL SPRING ISOLATION — Spring isolation may be
purchased as an accessory from Carrier for field installation. It
may also be field supplied and installed. Spring isolators may be
placed directly under machine support plates or located under
machine soleplates. See Fig. 14. Consult job data for specific ar-
rangement. Low profile spring isolation assemblies can be field
supplied to keep the machine at a convenient working height.
Obtain specific details on spring mounting and machine
weight distribution from job data. Also, check job data for
methods to support and isolate pipes that are attached to spring
isolated machines.
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Isolation package includes 4 elastomeric pads.
SOLEPLATE DIMENSIONS
ACCESSORY SOLEPLATE DETAIL
SOLEPLATE, HRS
FRAME SIZE 6: 1˝ (25) THK.;
FRAME SIZE 7: 1.25˝ (32) THK.
ELASTOMERIC PADS
Y-Y VIEW
Fig. 12 — Standard Isolation
1.5 in.
(38.1 mm)
(431.8 mm)
28 in.
25 in.
(711.2 mm)
(635 mm)
1.5 in.
(38.1 mm)
(355.6 mm)
X-X VIEW
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Accessory (Carrier supplied, field installed) soleplate package includes 4
soleplates, 16 jacking screws and leveling pads. Isolation package is also
required.
3. Jacking screws to be removed after grout has set.
4. Thickness of grout will vary, depending on the amount necessary to level
chiller. Use only pre-mixed non-shrinking grout, Ceilcote 748 or Embeco 636
Plus Grout, 1½ in. (38.1 mm) to 2¼ in. (57.2 mm) thick.
Fig. 13 —Accessory Isolation
NOTE: It is recommended that any installation other than the
ground floor should have spring isolation for the chiller and
piping vibration isolation.
NOTE: These isolators are not intended for seismic duty, but
are intended to reduce the vibration and noise levels transmit-
ted from the chiller to the surrounding environment. For instal-
lations adjacent to areas that are sensitive to noise and/or
vibration, use the services of a qualified consulting engineer or
acoustics expert to determine whether these springs will pro-
vide adequate noise/vibration suppression.
FRAME SIZE 6: 3/8" (10)
FRAME SIZE 7: 1/2" (13)
a19-2286
17 in.
7/8-9UNC-2B HOLES FOR
JACKING SCREWS
14 in.
/LEG
34
a23-46tf
a19-2002
FRAME SIZE 6: 0´-1 3/8˝ (35);
FRAME SIZE 7: 0´-1 3/4˝ (45)
a19-2276

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents