NOTE: The motor end of the 19XL compressor is heavy and
the compressor will tip to the motor end unless the motor
end is supported.
Additional Notes
1. Use silicon grease on new O-rings when refitting.
2. Use gasket sealant on new gaskets when refitting.
3. Cooler and condenser vessels may be rigged vertically.
Rigging should be fixed to all 4 corners of the tube sheet.

Install Chiller Supports

INSTALL STANDARD ISOLATION — Figures 10 and 11
show the position of support plates and shear flex pads, which
together form the standard chiller support system.
INSTALL ACCESSORY ISOLATION (if required) — Un-
even floors or other considerations may dictate the use of
HEAT EXCHANGER CODE
(Cooler/Condenser)
40-43
50-53
55-58
NOTE: Dimensions in parentheses ( ) are in millimeters.
Fig. 10 — 19XL Chiller Footprint
Fig. 11 — Standard Isolation
accessory soleplates (supplied by Carrier for field installa-
tion) and leveling pads. Refer to Fig. 10 and 12.
Level chiller by using jacking screws in isolation sole-
plates. Use a level at least 24-in. (600 mm) long.
For adequate and long lasting chiller support, proper grout
selection and placement is essential. Carrier recommends that
only pre-mixed, epoxy type, non-shrinking grout be used for
machine installation. Follow manufacturer's instructions for
applying grout.
1. Check chiller location prints for required grout
thickness.
2. Carefully wax jacking screws for easy removal from grout.
3. Grout must extend above the base of the soleplate and
there must be no voids in grout beneath the plates.
4. Allow grout to set and harden, per manufacturer's in-
structions, before starting chiller.
5. Remove jacking screws from leveling pads after grout has
hardened.
A
B
ft-in.
mm
ft-in.
mm
5-5
1670
13-0
3968
3
1
4
4
6-0
1
1835
13-0
1
3968
4
4
6-0
1
1835
17-8
3
5404
4
4
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Isolation package includes 4 shear flex pads.