Masonry Flue - Regency F2402M Owner's And Installation Manual

Freestanding woodfire
Table of Contents

Advertisement

6) Fasten the raincap with spark screens (if
required) to the top of your flue.
7) For optimum efficiency when installing into
a masonry flue, size accordingly, i.e. the 6"
(152mm) flue dia. is 28.28 sq.in.
8) To complete your flue installation, install the
double wall connector pipe from the heater's
flue collar to the flue support device.
9) If you are using a horizontal connector, the
flue connector should be as high as possible
while still maintaining the 18" (457mm) mini-
mum distance from the horizontal connector
to the ceiling.
10) NOTE: Residential Close Clearance and
Alcove installations require a listed dou-
ble wall connector from the heater collar
to the ceiling level.
CAUTION: At no time use unlabelled
parts, or substitute parts made for another
flue system.
Install as per flue manufacturer's instal-
lation instructions.
WARNING: Operate only with door fully
closed - open feed door to feed fire only.
F2400/S2400 Freestanding Woodfire
In addition to standard installation instructions
the following requirements are mandatory for
installation in a mobile home.
1) The heater must be permanently bolted to
the floor of the Mobile Home using the floor
screws provided.
2) The heater must have a permanent outside
air source for combustion.
3) The heater must be electrically grounded to
the steel chassis of the Mobile Home.
4) A listed double-wall connector flue system,
roof thimble, spark arrestor and roof flashing kit
suitable for use in Mobile Homes must be used.
5) If the flue exits the Mobile Home at a location
other than through the roof, and exits at a point
7ft. (2130mm) or less above the ground level
on which the Mobile Home is positioned a guard
or method of enclosing the flue shall be fitted at
the point of exit for a height up to 7ft. (2130mm).
6) The flue shall be attached directly to the room
heater and shall extend at least 3 ft. (914mm)
above the part of the roof through which it
passes. The top of the flue should project at
least 2ft. (610mm) above the highest elevation
of any part of the Mobile Home within 10 ft.
(3048mm) of the flue.
7) The flue system shall comply with Local
Requirements.
8) Any openings in a flue guard where required
must not permit the entrance of 3/4" (19mm)
diameter rod.
9) CAUTION: THE STRUCTURAL INTEGRITY
OF THE MOBILE HOME ROOF, FLOOR,
WALLS AND CEILING MUST BE MAIN-
TAINED.
10) Check any other local building code as other
local codes may apply.
11) WARNING: DO NOT INSTALL IN A SLEEP-
ING ROOM OF A MOBILE HOME.
12) Use silicone to create an effective vapour
barrier at the location where the flue or other
component penetrates to the exterior of the
structure.