Digital operator

Data display
Indicators
(Setting/Monitor
item indicators)
Operation keys
Appearance
e
Name
Data display
Frequency adjuster
Frequency
reference indicator
Output frequency
indicator
Output current
indicator
Multi-function
monitor indicator
Forward/Reverse
selection indicator
Local/Remote
selection indicator
Parameter setting
indicator
Mode Key
Increment Key
Decrement Key
Enter Key
RUN Key
STOP/RESET Key
.
Note:
1
The status of the local/remote selection indicator can be only monitored while the Inverter is in operation. Any RUN comand input is ignored while this
.
indicator is lit
.
2
While inverter is in operation, the parameters can be only monitored and only some parameters can be changed. Any RUN command is ignored while the
parameter setting indicator is lit.
.
3
For safety reasons, the reset function cannot be used while an operation instruction (forward/reverse) is being input. Turn the operation instruction OFF
before using this function.
4 . V7 IP65 types have digital operator without Frequency adjuster.
208
Displays relevant data items, such as frequency reference, output frequency, and parameter set
values.
Sets the frequency reference within a range between 0 Hz and the maximum frequency.
(See note 4.)
The frequency reference can be monitored or set while this indicator is lit.
The output frequency of the Inverter can be monitored while this indicator is lit.
The output current of the Inverter can be monitored while this indicator is lit.
The values set in U01 through U10 are monitored while this indicator is lit.
The direction of rotation can be selected while this indicator is lit when operating the Inverter with
the RUN Key.
The operation of the Inverter through the Digital Operator or according to the set parameters is
selectable while this indicator is lit. (See note 1.)
The parameters in n001 through n179 can be set or monitored while this indicator is lit.
(See note 2.)
Switches the simplified-LED (setting and monitor) item indicators in sequence.
Parameter being set will be canceled if this key is pressed before entering the setting.
Increases multi-function monitor numbers, parameter numbers, and parameter set values.
Decreases multi-function monitor numbers, parameter numbers, and parameter set values.
Enters multi-function monitor numbers, parameter numbers, and internal data values after they are
set or changed.
Starts the Inverter running when the 3G3MV is in operation with the Digital Operator.
Stops the Inverter unless parameter n007 is set to disable the STOP Key.
Used to reset the Inverter when an error occurs.
FREQUENCY
adjuster
Function
(See note 3.)