Trouble shooting 21
OUTDOOR UNIT Error Method:
2-way valve thermistor error
Detective Actuators:
Outdoor unit Main PCB
2-way valve temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature(°C)
Resistance Value (k )
Temperature(°C)
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
BLACK
1
1
1
WHITE
RED
3
2
2
WHITE
4
3
3
WHITE
YELLOW
4
5
4
CN39
WHITE
5
6
5
WHITE
BLUE
6
6
7
WHITE
8
7
7
WHITE
BLACK
8
8
9
WHITE
BLACK
1
1
1
RED
GRAY
2
2
2
RED
4
3
3
RED
BROWN
5
4
4
CN40
RED
6
5
5
RED
ORANGE
6
6
7
RED
8
7
7
GREEN
RED
9
8
8
RED
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When the 2-way valve temperature thermistor open or short-circuit is
detected at power ON or while running the compressor.
2.Thermistor failure
-30
-20
-10
1131.9
579.6
312.3
50
60
17.1
11.6
VALVE THERMISTOR A, B
2-WAY VALVE A
3-WAY VALVE A
2-WAY VALVE B
3-WAY VALVE B
VALVE THERMISTOR D (For AO G30LAT4)
2-WAY VALVE C
3-WAY VALVE C
2-WAY VALVE D
3-WAY VALVE D
3. Main PCB failure
0
10
176.0
103.3
70
80
8.1
5.8
02-24
20
30
40
62.9
39.6
25.6