7. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in the table 6.
(Table 6 : Compressor Operation Frequency Range)
AO*G18LAT3
AO*G24LAT3
AO*G30LAT4
2. OPERATION FREQUENCY CONTROL AT START UP
For
AO*G18/ 24LAT3
The compressor frequency soon after the start-up is controlled as shown in the figure 16.
(Fig.16 : Compressor Control at Start-up)
85rps
56rps
40rps
For
AO*G30LAT4
The compressor frequency soon after the start-up is controlled as shown in Figure 17.
(Fig.17 : Compressor Control at Start-up)
56rps
40rps
40rps
Cooling
Min
Max
20rps
100rps
20rps
90rps
60 - 780sec
120sec
180 - 900sec
60 - 720sec
180sec
240 - 900sec
Heating
Min
Max
24rps
110rps
20rps
95rps
120sec
300 - 1020sec
120sec
360 - 1020sec
01-21