DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
AG G09LVCA
AG  G12LVCA
AG  G14LVCA
AO G09LVCA
AO  G12LVCA
AO  G14LVLA

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu AG*G09LVCA

  • Page 1: Air Conditioner

    AIR CONDITIONER Floor type DESIGN & TECHNICAL MANUAL INDOOR AG G09LVCA AG  G12LVCA AG  G14LVCA OUTDOOR AO G09LVCA AO  G14LVLA AO  G12LVCA...
  • Page 2: Indoor Unit

    1.INDOOR UNIT FLOOR TYPE : AG G09LVCA AG  G12LVCA AG  G14LVCA DTR_AG005E_02 2013.07.19...
  • Page 3: Table Of Contents

    CONTENTS 1. INDOOR UNIT 1. FEATURES ......................01 - 01 2. WIRELESS REMOTE CONTROLLER ..........01 - 03 3. SPECIFICATIONS ....................01 - 05 4. DIMENSIONS ......................01 - 07 5. WIRING DIAGRAMS ..................01 - 08 6. CAPACITY TABLE ....................
  • Page 4: Features

    FEATURES MODEL „ „ AGG09LVCA / AOG09LVCA AO  G09/12LVCA AGG12LVCA / AOG12LVCA AGG14LVCA / AOG14LVLA AO  G14LVLA FEATURES „ „ Energy efficiency class „ MODEL AG  G09LVCA AG  G12LVCA AG  G14LVCA Cooling Heating All DC „...
  • Page 5: Economy Operation

    Flexible & easy installation „ Piping space is wide and connection work is easy. Beneath standard window Standard concave portion Wall Half concealed (Optional parts necessary) Min.940 Min. Min. Min. 730 Max. Max. 150 (unit:mm) (unit:mm) : t i : t i Choice of 6-direction drain &...
  • Page 6: Wireless Remote Controller

    WIRELESS REMOTE CONTROLLER FEATURES „ „ 4 mode timer setup available (ON / OFF / PROGRAM / SLEEP).  „ Easy operation.  „ Easy to change signal code (max. 4 units) by button operation.  „ Simple function setting „...
  • Page 7 FUNCTIONS „ „ Signal transmitter MODE button 10°C HEAT button SET TEMP. button ( ECONOMY button SLEEP button TIMER MODE button FAN button START/STOP button SET button SWING button TIMER set ( ) button CLOCK ADJUST button TEST RUN button •This button is used when installing the air conditioner, and should not be used under normal conditions, as it will cause the indoor unit’s thermostat function to operate incorrectly.
  • Page 8: Specifications

    SPECIFICATIONS FLOOR TYPE Type INVERTER HEAT PUMP Model name AGG09LVCA AGG12LVCA AGG14LVCA Power source 230 V~ 50 Hz Available voltage range 198–264V 2.60 3.50 4.20 Rated Btu/h 8,900 11,900 14,300 Cooling 0.9–3.5 0.9–4.0 0.9–5.0 Min.–Max. Btu/h 3,100–11,900 3,100–13,600 3,100–17,100 Capacity 3.50 4.50 5.20...
  • Page 9 Model name AGG09LVCA AGG12LVCA AGG14LVCA Cooling Energy efficiency class Heating (Average) Cooling 2.6 (35 °C) 3.5 (35 °C) 4.2 (35 °C) Pdesign Heating (Average) 2.9 (-10 °C) 3.8 (-10 °C) 4.7 (-10 °C) SEER Cooling 7.00 6.50 6.40 kWh/kWh SCOP Heating (Average) 4.20 4.00...
  • Page 10: Dimensions

    DIMENSIONS MODEL : AGG09LVCA, AGG12LVCA, AGG14LVCA „ „ (Unit : mm) Side view Front view INSTALLATION PLACE „ „ 10 cm or more 8 cm or more 8 cm or more 5 cm or more 15 cm or below from the floor AG ...
  • Page 11: Wiring Diagrams

    WIRING DIAGRAMS MODEL : AGG09LVCA, AGG12LVCA, AGG14LVCA „ „ TO OUTDOOR UNIT - (01 - 08) -...
  • Page 12: Capacity Table

    CAPACITY TABLE 6-1. COOLING CAPACITY MODEL : AGG09LVCA „ „ Indoor temperature °CDB °CWB °CDB 1.99 1.88 0.25 2.21 1.89 0.25 2.29 2.05 0.26 2.44 2.06 0.26 2.51 2.23 0.26 2.67 2.22 0.26 2.82 2.36 0.27 2.27 2.15 0.41 2.53 2.16 0.42 2.61...
  • Page 13: Heating Capacity

    6-2. HEATING CAPACITY This table is created using the maximum capacity. : AGG09LVCA MODEL „ „ 10.0 Indoor temperature °CDB °CDB °CWB 2.61 0.99 2.54 1.01 2.48 1.03 2.42 1.05 2.36 1.07 3.27 1.13 3.19 1.16 3.11 1.18 3.04 1.20 2.96 1.23 3.91...
  • Page 14: Fan Performance And Capacity

    FAN PERFORMANCE AND CAPACITY 7-1. AIR VELOCITY DISTRIBUTION MODEL : AGG09LVCA, AGG12LVCA, AGG14LVCA „ „ Unit : m/s TOP VIEW Conditions: FLOW CONTROL PANEL : Horiz. LOUVER : Center Fan speed : HI Operation mode : FAN Fan select : UPPER&LOWER : UPPER FAN : LOWER FAN LOWER...
  • Page 15: Airflow

    7-2. AIRFLOW MODEL : AGG09LVCA, AGG12LVCA „ „ Cooling „ Number of rotations Fan speed [r.p.m] Airflow (UPPER/LOWER) m³/h HIGH 1190/1000 m³/h 1000/850 m³/h 820/690 m³/h QUIET 660/560 zHeating „ Number of rotations Fan speed [r.p.m] Airflow (UPPER/LOWER) m³/h HIGH 1240/1040 m³/h 1040/880...
  • Page 16 MODEL : AGG14LVCA „ „ Cooling „ Number of rotations Fan speed [r.p.m] Airflow (UPPER/LOWER) m³/h HIGH 1330/1120 m³/h 1100/930 m³/h 890/750 m³/h QUIET 660/560 zHeating „ Number of rotations Fan speed [r.p.m] Airflow (UPPER/LOWER) m³/h HIGH 1330/1120 m³/h 1100/930 m³/h 860/730 m³/h...
  • Page 17: Operation Noise (Sound Pressure)

    OPERATION NOISE (SOUND PRESSURE) 8-1. NOISE LEVEL CURVE MODEL : AGG09LVCA „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 High High NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 Quiet NC-20 NC-20 Quiet NC-15 NC-15...
  • Page 18 MODEL : AGG14LVCA „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 High NC-50 NC-50 High NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 Quiet NC-20 NC-20 Quiet NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 19: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT Microphone Microphone Airflow ● ● Airflow - (01 - 16) -...
  • Page 20: Electric Characteristics

    ELECTRIC CHARACTERISTICS Model Name AGG09LVCA AGG12LVCA AGG14LVCA Voltage 230 ~ Power Supply Frequency Max Operating Current Connection Cable Wiring Spec. * Limited wiring length *: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. - (01 - 17) -...
  • Page 21: Safety Devices

    SAFETY DEVICES Model AGG09LVCA Protection form AGG12LVCA AGG14LVCA Circuit protection Current fuse (PC board) 250 V 3.15 A Terminal protection Current (thermal) fuse 250 V 3 A OFF : 150 ± 15 °C Fan motor protection Terminal protection program ON : 120 ± 15 °C - (01 - 18) -...
  • Page 22: External Input & Output

    EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS CN14 Control input See external input/output settings for details. CN20 Operation status output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) „ „ The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
  • Page 23 Parts (Optional) „ Parts name Model name External connect kit UTY-XWZX - (01 - 20) -...
  • Page 24: External Output

    11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT „ „ An air conditioner operation status signal can be output. Circuit diagram example „ Indoor unit Connected unit control PC board Connector Ex.) Relay unit Ex.) Display DC 24 V Relay power supply Relay spec.: Max.DC 24 V, 10 mA to less 10 m*...
  • Page 25: Function Settings

    FUNCTION SETTINGS 12-1. INDOOR UNIT (Setting by remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings may cause an indoor unit malfunction. • After turning on the power, perform the Function Setting according to the installation conditions by using the remote controller.
  • Page 26 CONTENTS OF FUNCTION SETTING „ „ • Follow the instructions in the Local Setup Procedure, which is supplied with the remote controller, in accordance with the installed condition. After turning on the power, perform the Function Setting by using the remote controller. •...
  • Page 27 4) Room temperature control for heating Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment. (  . . .Factory setting) Setting Description Function Number Setting Value Standard ...
  • Page 28 8) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. (  . . .Factory setting) Setting Description Function Number Setting Value Operation/Stop mode  (Setting prohibited) Forced stop mode 9) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
  • Page 29 REMOTE CONTROLLER SIGNAL CODE SETTING „ „ Use the following steps to select the signal code of the remote controller. (Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code.) Press the START/STOP button until only the clock is displayed on the remote controller display.
  • Page 30: Optional Parts

    OPTIONAL PARTS 13-1. CONTROLLERS Exterior Parts name Model No. Summary Large and full-dot liquid crystal Wired remote screen, wide and large keys UTY-RVN  M controller easy to press, user-intuitive arrow key. The room temperature can be Wired remote controlled by detecting the UTY-RNN ...
  • Page 31: Outdoor Unit

    2. OUTDOOR UNIT SINGLE TYPE : AOG09LVCA AOG12LVCA AOG14LVLA DTR_AO129E_01 2012.12.04...
  • Page 32 CONTENTS 2. OUTDOOR UNIT 1. SPECIFICATIONS ....................02 - 01 2. DIMENSIONS ......................02 - 02 3. REFRIGERANT CIRCUIT ................02 - 03 4. WIRING DIAGRAMS ..................02 - 04 5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE ..................
  • Page 33: Specifications

    SPECIFICATIONS Type INVERTER HEAT PUMP Model name AOG09LVCA AOG12LVCA AOG14LVLA Power source 230V~ 50Hz Available voltage range 198 - 264V~ 50Hz Starting current Cooling 1,680 1,910 Airflow rate Heating 1,490 1,680 1,750 Type × Q'ty Propeller fan × 1 Propeller fan × 1 Propeller fan ×...
  • Page 34: Dimensions

    DIMENSIONS MODEL : AOG09LVCA, AOG12LVCA „ „ (Unit : mm) MODEL : AOG14LVLA „ „ INSTALLATION PLACE „ „ 100 mm or more 600 mm or more 100 mm or more 250 mm or 200 mm or more more 50 mm or more - (02 - 02) -...
  • Page 35: Refrigerant Circuit

    REFRIGERANT CIRCUIT MODEL : AOG09LVCA, AOG12LVCA, AOG14LVLA „ „ Indoor unit 3-Way Heat exchanger valve Muffler 2-Way valve 4-Way valve Strainer Expansion valve Strainer Outdoor unit Heat exchanger Cooling Heating : Thermistor (Discharge Temp.) : Thermistor (Outdoor Temp.) : Thermistor (Heat Exchanger Out Temp.) : Thermistor (Room Temp.) : Thermistor (Pipe Temp.) Refrigerant pipe diameter...
  • Page 36: Wiring Diagrams

    WIRING DIAGRAMS MODEL : AOG09LVCA, AOG12LVCA „ „ - (02 - 04) -...
  • Page 37 MODEL : AOG14LVLA „ „ - (02 - 05) -...
  • Page 38: Capacity Compensation Rate For Pipe Length And Height Difference

    CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE MODEL : AOG09LVCA, AOG12LVCA „ „ Pipe length (m) COOLING 0.915 0.905 Û 1 0.955 0.922 0.912 Indoor unit is higher than 0.974 0.959 0.926 0.916 outdoor unit. 0.992 0.978 0.963 0.930 0.920 Height...
  • Page 39 MODEL : AOG14LVLA „ „ Pipe length (m) COOLING 0.950 0.946 Û 1 0.976 0.958 0.954 Indoor unit is higher than 0.984 0.980 0.962 0.958 outdoor unit. 0.992 0.988 0.984 0.966 0.962 Height 1.000 0.996 0.992 0.974 0.969 difference H 1.000 0.996 0.992...
  • Page 40: Additional Charge Calculation

    ADDITIONAL CHARGE CALCULATION MODEL : AOG09LVCA, AOG12LVCA „ „ Refrigerant type R410A Refrigerant amount 1,050 Refrigerant charge „ Total pipe length 15 or less 20 (MAX) 20g/m Additional charge MODEL : AOG14LVLA „ „ Refrigerant type R410A Refrigerant amount 1,150 Refrigerant charge „...
  • Page 41: Airflow

    AIRFLOW MODEL : AOG09LVCA „ „ Cooling „ Number of rotations Airflow (r.p.m.) 1,680 Heating „ Number of rotations Airflow (r.p.m.) 1,490 MODEL : AOG12LVCA „ „ Cooling „ Number of rotations Airflow (r.p.m.) 1,680 Heating „ Number of rotations Airflow (r.p.m.) 1,680...
  • Page 42 MODEL : AOG14LVLA „ „ Cooling „ Number of rotations Airflow (r.p.m.) 1,910 1,124 Heating „ Number of rotations Airflow (r.p.m.) 1,750 1,030 - (02 - 10) -...
  • Page 43: Operation Noise (Sound Pressure)

    OPERATION NOISE (SOUND PRESSURE) 8-1. NOISE LEVEL CURVE MODEL : AOG09LVCA „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000...
  • Page 44 MODEL : AOG14LVLA „ „ Cooling Heating „ „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency,Hz Octave band center frequency,Hz - (02 - 12) -...
  • Page 45: Sound Level Check Point

    8-2. SOUND LEVEL CHECK POINT - (02 - 13) -...
  • Page 46: Electric Characteristics

    ELECTRIC CHARACTERISTICS Model name AOG09LVCA AOG12LVCA AOG14LVLA Voltage 230 ~ Power supply Frequency *1) Max operating current 10.0 13.5 Starting Current Main Fuse (Circuit breaker) Current *2) Wiring Spec.: Power Cable 1.5 - 2.5 *3) Limited wiring length : *1) The maximum current is the total current of indoor unit and outdoor unit. *2) Wiring Spec.: Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
  • Page 47: Safety Devices

    SAFETY DEVICES Model Protection form AOG09LVCA AOG12LVCA AOG14LVLA 250V 20A Current fuse (Near the terminal) 250V 5A Circuit protection 250V 15A Current fuse (Main printed circuit board) 250V 3.15A OFF: 100 °C Thermal protection Fan motor protection program ON: 95 °C Thermal protection OFF: 110°C...