Measuring Ranges Of The Analog Input Modules In S7 Format - Siemens ET 200pro Operating Instructions Manual

Small, extremely rugged and high-performance i/o system with ip65/66/67 degree of protection
Hide thumbs Also See for ET 200pro:
Table of Contents

Advertisement

Analog electronic modules

15.11 Measuring ranges of the analog input modules in S7 format

15.11
Measuring ranges of the analog input modules in S7 format
Voltage measuring ranges: 1 to 5 V
Measuring range
1 to 5 V
> 5.704 V
5.704 V
5 V
4 V
1 V + 144.7 µV
1 V
0.296 V
< 0.296 V
Voltage measuring ranges: 0 to 10 V
Measuring range
0 to 10 V
> 11.759 V
11.759 V
10 V
7.5 V
0 V + 361.7 µV
0 V
-1.759 V
< -1.759 V
438
Units
Decimal
Hexadecimal
32767
7FFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
0001
0
0000
-1
FFFF
-4864
ED00
32767
7FFF
- 32768
8000
Units
Decimal
Hexadecimal
32767
7FFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
0001
0
0000
-1
FFFF
-4864
ED00
- 32768
8000
Overflow
H
Overrange
H
H
Nominal range
H
H
H
H
Underrange
H
H
Wire break
H
Underflow
H
Overflow
H
Overrange
H
H
Nominal range
H
H
H
H
Underrange
H
H
Underflow
H
Operating Instructions, 03/2013, A5E00335544-08
Range
Range
ET 200pro distributed I/O system