Daikin RXG-E2V1B Technical Data Manual page 7

Outdoor units, pair application
Table of Contents

Advertisement

3
Electrical data
RXG+FTXG-E
Representative unit combination
Indoor unit
FTXG35EV1BW
3
FTXG35EV1BS
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps (A)
W
: Fan Motor Rated Output (W)
RHz
: Rated operating frequency(Hz)
6
• Outdoor Units • R-410A • RXG-E2V1B
Outdoor unit
Hz-volts
50 - 220
RXG35E2V1B
50 - 230
50 - 240
50 - 220
RXG35E2V1B
50 - 230
50 - 240
• Split Sky Air • Outdoor Units
Power supply
Vol t age range
MCA
MFA
Max. 50Hz 264V
12
15
Min. 50Hz 198V
Max. 50Hz 264V
12
15
Min. 50Hz 198V
NOTES
1
RLA is based on the following conditions:
Indoor temperature 27°CDB/19°CWB
Outdoor temperature 35°CDB
2
Maximum allowable voltage variation between phases is 2%
3
Select wire size based on the larger value of MCA.
4
Instead of fuse, use circuit breaker
5
For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ''E-Data Books''.
Finally, click on the document title of your choice.
Comp.
OFM
RHz
RLA
W
FLA
W
4.9
0.23
80
4.7
35
0.22
40
4.5
0.21
4.9
0.23
80
4.7
35
0.22
40
4.5
0.21
IFM
FLA
0.52
0.50
0.48
0.52
0.50
0.48
3D045221B