Buderus supplies cascade systems in TL and TR
configurations:
TL: Inline installation
All boiler assemblies are in a line enabling an easy-to-monitor
installation in a narrow room.
TR: Back-to-back installation
The boiler assemblies are located on both sides of the frame
and are installed back-to-back to create a compact installation
which ideally suits rectangular rooms and which ensures the
best possible access to all boilers.
The relevant configuration can be selected on the basis of the
performance required (see table 1).
Boiler assembly connection kit
The connection kit can be used both for the Logamax plus
GB162-80 and for the 100-kW version. The connection kit
includes a pressure relief valve, a non-return valve, a pump
and isolating valves.
Low loss
TL- configuration
header
(inline)
2½"
TL2, TL3
3"
TL4
4"
TL5, TL6, TL7, TL8
Table 2 Low loss header configuration
Bend sets with low loss header
The Logamax plus GB162 cascade system can be installed in
various configurations (fig. 4). By using the bend set the low
loss header can be installed at an angle to the boilers. The gas
pipe is reversible so that the gas connection can be at the other
side of the boilers to the flow and return connections to the
header.
We reserve the right to make technical modifications.
Installation instructions Logamax plus GB162-80/100 cascade unit • Version 01/2006
TR- configuration
(back-to-back)
TR2
TR3, TR4
TR5, TR6, TR7, TR8
Items supplied with unit
Appliance
Cascade
performance
system options
TL = inline
[kW]
TR = back-to-back
80
Single installation
100
Single installation
160
TL2 or TR2
180
TL2 or TR2
200
TL2 or TR2
240
TL3 or TR3
260
TL3 or TR3
280
TL3 or TR3
300
TL3 or TR3
340
TL4 or TR4
360
TL4 or TR4
380
TL4 or TR4
400
TL4 or TR4
440
TL5 or TR5
460
TL5 or TR5
480
TL5 or TR5
500
TL5 or TR5
520
TL6 or TR6
540
TL6 or TR6
560
TL6 or TR6
580
TL6 or TR6
600
TL6 or TR6
620
TL7 or TR7
640
TL7 or TR7
660
TL7 or TR7
680
TL7 or TR7
700
TL7 or TR7
720
TL8 or TR8
740
TL8 or TR8
760
TL8 or TR8
780
TL8 or TR8
800
TL8 or TR8
Table 1 Cascade selection
2
1
2
1
2
1
Fig. 4
Cascade system configuration varieties
W
• http://www.buderus-commercial.co.uk
2
Number of boilers
Logamax plus
GB162
80
100
1
1
2
1
1
2
3
2
1
1
2
3
3
1
2
2
1
3
4
3
2
2
3
1
4
5
4
2
3
3
2
4
1
5
6
4
3
3
4
2
5
1
6
7
4
4
3
5
2
6
1
7
8
2
1
2
1
2
1
5

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Gb162-80