Structure Of Configuration Data Block (Cdb) - Siemens SIMATIC NET CP 243-1 IT Technical Manual

Communications processor for industrial ethernet and information technology
Table of Contents

Advertisement

Configuration
4.4.2

Structure of Configuration Data Block (CDB)

The CDB is created by the Internet wizard in STEP 7 Micro/WIN 32. The structure
of the CDB is shown below in the following table.
Byte Offset
in Variable
Memory
Header
0-4
Module name
5-6
Length of the CDB
7-8
Length of the NPB
General information
9
Internal system use
10
Internal system use
11-12
Reserved for STEP 7 Micro/WIN 32
13-14
Common flag
Bit [0] Duplex mode
Bit [1] Data rate
Bit [2] Auto negotiation
Bit [3] BOOTP
Bit [4-7] Not used
Bit [8-15] CRC validation
15-18
Configured IP address
This field should be set to
16#00000000 when BOOTP is being
used.
19-22
Configured subnet mask
This field should be set to
70
Description
0: Half duplex
1: Full Duplex
0: 10 Mbit/sec
1: 100 Mbit/sec
0: No auto negotiation
1: Auto negotiation
0: Use configured network pa-
rameters
1: BOOTP
16#00 CRC check activated
16#AC CRC check deactivated
Data Format
5 bytes, ASCII
16#4350323433
"CP243"
2 bytes, hex
16#006C
(108, decimal)
2 bytes, hex
16#0014
(20, decimal)
1 byte, hex
1 byte, hex
2 bytes, hex
2 bytes, hex
16#0004:
Auto negotiation
Use configured net-
work parameters
CRC check activated
16#AC04:
Auto negotiation
Use configured net-
work parameters
CRC check activated
4 bytes, hex
192.12.45.23:
16#C00C2D17
4 bytes, hex
255.255.255.0:
16#FFFFFF00
J31069-D0429-U001-A0-7618
03/03
Example
CP 243-1 IT

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp 243-1 it

Table of Contents