STEP
Check RPM feedback line. To do this, connect a DC voltmeter across terminals
PL3-2 ORANGE (+) and PL3-3 VIOLET (-). Repeat COMPONENT TEST by
turning setup switch SW-6 OFF and then back ON. Does voltage across OR-
48.
ANGE and VIOLET wires change between states as shown below?
• State 1—OFF (12.0 — 12.5 vdc)
• State 2—LOW (10.7 — 11.7 vdc)
• State 3—HIGH (9.7 — 10.7 vdc)
Connect a DC voltmeter across ORANGE (+) and VIOLET (-) wires at connec-
tor PL13. Repeat COMPONENT TEST by turning setup switch SW-6 OFF and
then back ON. Does voltage across ORANGE and VIOLET wires change be-
49.
tween states as shown below?
• State 1—OFF (12.0 — 12.5 vdc)
• State 2—LOW (10.7 — 11.7 vdc)
• State 3—HIGH (9.7 — 10.7 vdc)
You have an open wire or bad terminal on either the ORANGE or VIOLET wire
50.
between connectors PL13 and PL3. Repair it or replace blower harness(es).
37
YES
NO
GO TO
22
49
50
33
17