NOTE
The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate insulation, shorten component life
and cause malfunctions.
Keep the installation environment per standard described as follows:
No.
Item
1
Installation
location
2
Ambient
temperature
3
Relative humidity
4
Altitude
5
Dust
6
Inflammable gas
following
IEC654-4
Part 4
4
G9000 Enhanced Series UPS Installation and Operation Manual – 93823-004
WARNING 3
Table 2–1 UPS Installation Environment
Environment standard
Minimum temperature: 32 °F(0 °C)
Maximum temperature: 104 °F(40 °C)
The average temperature over any 24-hour period must be in the range
41 °F (5 °C) to 95 °F(35 °C).
The relative humidity must be held between 5 and 95%.
There must be no condensation due to temperature changes.
This equipment must not be applied at altitude that exceeds
2250m (7380ft) above sea level.
Dust in the room where the UPS is installed must not exceed normal
atmospheric dust levels. In particular, that dust should not include iron
particles, oils or fats, or organic materials such as silicone.
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
S)
2
Sulfurous acid gas (SO
Chlorine gas (Cl
)
2
Ammonia gas (NH
)
3
Nitrous oxides (NO
)
x
Ozone (O
)
3
Indoors
No more than 0.003 PPM
)
No more than 0.01 PPM
2
No more than 0.002 PPM
No more than 1 PPM
No more than 0.05 PPM
No more than 0.002 PPM