Controller Failure Symptoms; Table 7-4 Controller Failure Symptoms - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Troubleshooting/Service
Lower
Display
IN1RNG
Input 1 out of range. The process input
is outside the range limits.
PV out of range.
PV LIM
PV = INP1 + INP1 BIAS

7.6 Controller Failure Symptoms

Introduction
In addition to the error message prompts, there are failure symptoms that can be identified
by noting how the controller displays and indicators are reacting.
Symptoms
Compare your symptoms with those shown in Table 7-4.
Upper
Display
Display
Blank
OK
Displayed
disagrees with
controller
OK
Display does not function when a key is pressed
58
Reason for Failure

Table 7-4 Controller Failure Symptoms

Lower
Indicators
Blank
Off
OK
Output
output
OK
OK
UDC2300 Limit Controller Product Manual
How to Correct the Problem
1. Make sure the range and actuation are
configured properly.
2. Check the input source.
3. Restore the factory calibration.
(See Subsection 6.6.)
4. Field calibrate.
See Section 6- Input Calibration.
1. Make sure the input signal is correct.
2. Make sure the Bias settings are correct.
3. Recheck the calibration. Use Bias of 0.0
Controller
Probable
Output
Cause
None
Power Failure
Relay Output
Controller
Output
disagrees with
displayed
output
External Alarm
Malfunction in
function does
alarm output
not operate
properly
Keyboard
Malfunction
Trouble-
shooting
Procedure
1
2
3
4