Preliminary Information; Figure 6-1 Input 1 Wiring Terminals - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Sensor Type
T (low)
W5W26
W5W26 (low)
Radiamatic
Type RH
Type RI*
RTD
(IEC Alpha=0.00385)
100 ohms
100 ohms (low)
200 ohms
500 ohms
Linear
Milliamps
(impedance – 249 Ω)
Millivolts
Volts

6.3 Preliminary Information

Disconnect the Field Wiring
Tag and disconnect any field wiring connected to the input 1 terminals on the rear of the
controller.
1/01
PV Input Range
°F
-200 to 500
–129 to260
0 to 4200
–18 to2315
0 to 2240
–18 to1227
0 to 3400
–18 to1871
0 to 3200
–18 to1760
-300 to 1200
–184 to649
-300 to 300
–184 to149
-300 to 900
–184 to482
-300 to 900
–184 to482
4 to 20 mA
0 to 20 mA
0 to 10 mV
0 to 50 mV
0 to 100 mV
1 to 5 Volts
0 to 2 Volts
0 to 5 Volts
0 to 10 Volts*
+
_
Input 1
Connections
R

Figure 6-1 Input 1 Wiring Terminals

UDC2300 Limit Controller Product Manual
°C
0 %
–4.149 mV
–0.234 mV
–0.234 mV
0.00 mV
0.00 mV
25.18 ohms
25.18 ohms
50.36 ohms
125.90 ohms
4.00 mA
0.00 mA
0.00 mV
0.00 mV
0.00 mV
1.00 Volts
0.00 Volts
0.00 Volts
0.00 Volts
8
7
6
Input Calibration
Range Values
100 %
12.574 mV
37.075 mV
22.283 mV
57.12 mV
60.08 mV
274.96 ohms
156.90 ohms
549.92 ohms
1374.80 ohms
20.00 mA
20.00 mA
10.00 mV
50.00 mV
100.00 mV
5.00 Volts
2.00 Volts
5.00 Volts
10.00 Volts
45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents