Installation
2.4 Limit Control and Alarm Relay Contact Information
Limit Control Relays
Limit Control relays are designed to operate in a Failsafe mode. This results in momentary
(5 seconds maximum) limit action when power is initially applied, until the unit completes self-diagnostics.
If power is lost to the unit, the Limit Control Relay will still function.
Unit
Power
Off
On
Alarm Relays
Alarm relays are designed to operate in a Failsafe mode (that is, de-energized during alarm sate). This
results in alarm actuation when power is OFF or when initially applied, until the unit completes self-
diagnostics. If power is lost to the unit, the alarms will function.
Unit
Power
Off
On
8
Table 2-3 Limit Control Relay Contact Information
Limit Control Relay
Jumper
N.O.
N.C.
N.O.
N.C.
Table 2-4 Alarm Relay Contact Information
Alarm Relay
Variable NOT in Alarm State
Wiring
Relay
Contact
N.O.
Open
N.C.
Closed
N.O.
Closed
N.C.
Open
UDC2300 Limit Controller Product Manual
Variable NOT in
Limit State
Relay
Contact
Indicator
Open
Off
Closed
Closed
Off
Open
Variable in Alarm State
Indicators
Relay
Contact
Open
Off
Closed
Open
Off
Closed
Variable IN
Limit State
Relay
Contact
Indicator
Open
Off
Closed
Open
On
Closed
Indicators
Off
On