Miscellaneous Closing (Arming) Reporting Codes; Miscellaneous Opening (Disarming) Reporting Codes - DSC PC1404 Description

Hide thumbs Also See for PC1404:
Table of Contents

Advertisement

[330]-[334] Tamper/Restore Reporting Codes, Zones 01-8
These reporting codes are used by the communicator to transmit zone tampers and restores for Zones 1 to 8. These reporting codes are
sent to the Tamper Alarm & Tamper Restore call direction group of the system.
[338] Miscellaneous Tamper Reporting Codes
General System Tamper & Restore
These reporting codes are sent to the system Tamper Alarm & Tamper Restore call direction group when a panel tamper occurs.
Keypad Lockout
Whenever the system enters keypad lockout, this reporting code is sent to the system Tamper Alarm & Tamper Restore call direction
group.
[339]-[340] Closing (Arming) Reporting Codes (Access Codes 1-32)
When the system is armed, a closing reporting code is transmitted after the exit delay expires for the user code that armed the system.
These reporting codes are sent to the Opening & Closing call direction group of the system. In addition, "Armed in Stay Mode,"
"Armed in Away Mode" or "Armed in Night Mode" is logged to the event buffer.

[341] Miscellaneous Closing (Arming) Reporting Codes

Automatic Zone Bypassing
This stops transmission of zone bypass information for systems set up for an automatic communication format (SIA and Contact ID).
Enter [00] to disable the automatic zone bypassing communications. If the zones are to be identified, they are transmitted with the Par-
tial Closing to the Opening & Closing call direction group. (24 Hour zone types transmit that they have been bypassed when the user
exits the bypassing menu).
Partial Closing
If zones were manually bypassed at the time of arming, this reporting code is transmitted to the central station with the Closing code to
warn of a security compromise. Automatic bypasses caused by Stay arming do not cause this code to be transmitted. Zones force armed
by automatic arming transmit in the manner described above. If SIA is used, each zone is identified using the UB-XX (un-typed bypass)
identifier. The identified zones follow the partial closing code and precede the closing transmission. This reporting code is sent to the
Opening & Closing call direction group.
Special Closing
This reporting code is transmitted if the system is armed without an access code using Keyswitch Zone, Downloading, Quick Arm
[,][0], or Stay or Away function keys. In addition, either "Armed in Stay Mode," "Armed in Away Mode," or "Armed in Night Mode"
is logged to the event buffer for all closing types. This reporting code is sent to the Opening & Closing call direction group.
Late to Close
This reporting code is transmitted whenever the auto-arm pre-alert sounds (if the Late to Close option is enabled).
Exit Fault
If an Exit Error occurs and entry delay expires before the system is disarmed, this reporting code is sent. This reporting code is sent to
the Openings & Closings call direction group
If the delay zone that caused the exit error has cross zoning enabled, the exit fault and zone alarm still transmit if a second
i
zone is not violated. This is to inform the central station that the premise is not secure. The local alarm sequence follows
the cross zoning rules. The exit error is transmitted with the zone alarm that caused the fault, even if that zone has a trans-
mission delay enabled.
[342]-[343] Opening (Disarming) Reporting Codes (Access Codes 1-32)
When the system is disarmed, an opening Reporting code for the corresponding user is transmitted.
These reporting codes are sent to the Opening & Closing call direction group.

[344] Miscellaneous Opening (Disarming) Reporting Codes

Auto-Arm Cancellation
This reporting code is transmitted if Auto-Arming is Cancelled or Postponed.
Special Opening
If the system is disarmed (opened) by using keyswitch zone or downloading, this reporting code is transmitted to the Opening & Clos-
ing call direction group.
[345]-[346] Maintenance Alarm and Restore Reporting Codes
Battery Trouble & Restore
This trouble is reported if the standby battery is low or disconnected. These reporting codes are sent to the System Maintenance call
direction group.
AC Failure Trouble & Restore
If the AC supply has failed or has been restored, these reporting codes are sent. A programmable delay (001-255 minutes, Section
[377]) applies to both the trouble and the restore. These reporting codes are sent to the System Maintenance call direction group.
Bell Circuit Trouble
An open or short circuit detected across bell terminals causes this trouble to be reported.
.
PC1404 Programming Descriptions
15