Fire Trouble & Restore
An open circuit or any Low Sensitivity, Tamper or Fault report from a smoke detector causes this trouble to be reported. These reporting
codes are sent to the System Maintenance call direction group.
Auxiliary Power Supply Trouble & Restore
If an auxiliary voltage supply trouble occurs (the Aux PTC has caused the auxiliary supply to stop outputting power), this trouble is
reported. These reporting codes are sent to the System Maintenance call direction group.
When the Aux Positive Temperature Co-efficient (electronic fuse) enters the open state due to a short or high current draw,
i
if the short is removed and a load is still applied, the Aux+ output will not recover. It must be powered down and back up
again to restore this condition.
TLM Alarm
The TLM Restore code is sent when the telephone trouble condition is restored. This reporting code is sent to the System Maintenance
call direction group.
General System Trouble & Restore
These reporting codes are transmitted via System Maintenance call direction group to report hardware fault troubles that occur on the
system.
General System Supervisory Trouble & Restore
These reporting codes are transmitted via the System Maintenance call direction group when an enrolled TLXXX module has been
detected as absent or restored.
System Reset (Cold Start)
In the event of a total power failure, the Cold Start reporting code is transmitted to the central station when power is restored to the
panel. The reporting code is sent after 2 minutes to allow the panel to stabilize, although the event is logged in the buffer at 00:00. An
entry of 00 in this section disables the reporting code.

[347] Miscellaneous Maintenance Reporting Codes

Failure to Communicate (Phone Numbers 1, 2, 3 & 4)
When events fail to communicate to either telephone number, this reporting code is transmitted the next time a communication is suc-
cessful. The information is transmitted in the following order:
Old Event(s)
Failure To Communicate (Phone #1)
New Event(s)
The FTC reporting code does not follow any call direction "group." It is sent to every group's call directions upon transmission of
"failed to communicate" events. When event(s) fail to communicate to a telephone number, no attempt to communicate is made again
until another event is sent to that phone number.
Event Buffer 75% Full
This reporting code is generated after 96 events have been logged to the system event buffer since the panel was last uploaded with
DLS. This reporting code is sent to the system maintenance call direction group.
DLS Lead In and Lead Out
When call-back is enabled, the control panel transmits the DLS Lead In reporting code before calling back the downloading computer.
The DLS Lead Out reporting code is transmitted by the panel every time DLS has completed a successful DLS session with the control
panel. The DLS Lead In reporting code is transmitted in two ways: after the panel has been successfully called by DLS, but before the
panel calls DLS back via the downloading telephone number when call-back is enabled, or upon a user-initiated call-up. These report-
ing codes are sent to the System Maintenance call direction group.
i
If DLS is terminated by an alarm, the alarm system will not communicate the DLS lead out event.
General Zone Fault & Restore
This reporting code is sent whenever a zone has entered the fault state. This occurs when there is a short on DEOL hardwired zones.
These reporting codes are sent to the System Maintenance call direction group.
Delinquency Reporting Code
The Delinquency Reporting code is transmitted in one of two ways. If Section [380] Option [8] is OFF, it is transmitted when the sys-
tem has not been armed for the number of days programmed in Section [377]. If Section [380] Option [8] is ON, it is transmitted when
no zone activity has been detected on the system for the number of hours programmed in Section [377]. This reporting code is sent to
the System Maintenance call direction group.
The Activity Delinquency timer is active when the system is armed in Stay mode, and not active in Away mode or Night
i
mode arming.
Installer Lead In and Lead Out
The Installer Lead In and Lead Out reporting codes are sent when the panel enters and exits Installer Programming respectively.