Unspecified Voltage (Between Indoor And Outdoor Units) - Daikin FVKS25BVMB Service Manual

Inverter pair floor standing type b-series
Hide thumbs Also See for FVKS25BVMB:
Table of Contents

Advertisement

Troubleshooting
4.8
Unspecified Voltage
UA
Remote
Controller
Display
Method of
The supply power is detected for its requirements (different from pair type and multi type) by the
indoor / outdoor transmission signal.
Malfunction
Detection
Malfunction
The pair type and multi type are interconnected.
Decision
Conditions
Supposed
Causes
Troubleshooting
92
(between Indoor and Outdoor Units)
Wrong models interconnected
Wrong indoor unit PCB mounted
Indoor unit PCB defective
Wrong outdoor unit PCB mounted or defective
Be sure to turn off power switch before connect or disconnect connector,
Be sure to turn off power switch before connect or disconnect connector,
Caution
Caution
or parts damage may be occurred.
or parts damage may be occurred.
Check the indoor and outdoor unit
Check the indoor and outdoor unit
model numbers.
model numbers.
Indoor unit and outdoor unit
Indoor unit and outdoor unit
matched?
matched?
YES
YES
Check the code numbers
Check the code numbers
(2P01234, for example) of the
(2P01234, for example) of the
indoor and outdoor unit PCB
indoor and outdoor unit PCB
with the Parts List.
with the Parts List.
Matched compatibly?
Matched compatibly?
YES
YES
NO
NO
NO
NO
SiBE06-514A
Match the compatible
Match the compatible
models.
models.
Change for the specified
Change for the specified
PCB (1) or (2).
PCB (1) or (2).
Replace the indoor unit
Replace the indoor unit
PCB (1) (or the outdoor unit
PCB (1) (or the outdoor unit
PCB).
PCB).
(Q0347)
(Q0347)
Service Diagnosis