Daikin FVKS25BVMB Service Manual page 150

Inverter pair floor standing type b-series
Hide thumbs Also See for FVKS25BVMB:
Table of Contents

Advertisement

SiBE06-514A
Step
5
Undo the hooks.
Pull and remove the
front panel.
3. Remove the fan motor.
1
Unscrew the washer-
fitted nut (M10) of the
propeller fan with a
spanner.
Remove the propeller
2
fan.
Removal Procedure
Procedure
Outdoor Unit
Points
The front panel has 4 hooks.
The fan motor is united with
the front panel.
The screw has reverse
winding.
Align
mark of the
propeller fan with D-cut
section of the motor shaft
when reassembling.