Technical Data; Technical And Physical Data For Arc (Cool Only) And Arg (Cool Only + Gas Heat) - York ARC 045 Installation Manual

Roof top air conditioners activa series
Table of Contents

Advertisement

1
Installation manual
1.4

Technical data

Place separators -1- above the unit to prevent the ca‐
bles or slings from touching it.
Attach guide ropes so that that the unit does not rotate
freely.
The cables or slings should be long enough to form
an angle of over 45º to the horizontal plane. Hoist the
unit keeping it in a horizontal position.
D A N G E R
There should not be onlookers within a radius of 10
m of the unit when it is being hoisted.
Centre of gravity of the unit
Models
045
A
1180
B
1390
C
3180
D
2337
All measurements in mm.
1. Centre of gravity
2. End of the outdoor coil
1.4 Technical data
1.4.1 Technical and physical data for ARC (cool only) and ARG (cool only
+ gas heat)
Models
Cooling capacity(1)
Rated absorbed power in cool mode
Optional electric heating capacity (400
Heating (ARC)
Heat capacity at 100% power (standard)
Heat capacity at 100% power, high ca‐
Gas Heating (ARG)
100% gas consumption (2ND-H natural
gas, G20 at 20 mbar and 15ºC) (stand‐
100% gas consumption (2ND-H natural
gas, G20 at 20 mbar and 15ºC) high ca‐
Compressors
Refrigerant (R-410A)
Electric power supply
Indoor fan (3)
4
060
075
090
1180
1135
1080
1425
1480
1540
3180
3495
3495
2337
2337
2337
ARC/ARG
Net cooling capacity
V) (2)
(LHV) Total
pacity (optional)
ard)
pacity (optional)
Stages
Rated/start-up current
Type and quantity
Degree of protection
Rated air flow
045
060
kW
45,1
61
kW
16
23
kW
kW
Net (2) kW
Total kW
Net (2) kW
3
m
/h
3
m
/h
No.
A
2x12/95
2x15/118
SCROLL, 1 (TANDEM 50% + 50%)
kg
10,5
18,2
V / ph / Hz
3
m
/h
8500
11500
075
090
71,5
84
30
36
12-25-37-50
85
76
100
90
8,6
9,8
2
2x20/140
2x25/198
IP21
20,5
29
400/3+N/50
13500
16000

Hide quick links: