Instructions For Starting Up The Unit; Electrical Checks - York ARC 045 Installation Manual

Roof top air conditioners activa series
Table of Contents

Advertisement

1.16 Instructions for starting up the unit

1.16.1 Electrical checks

Remove the transport fastening from the compres‐
sors
The compressors have a fastening system to prevent
them from moving during transport.
Once the unit is installed and before making its initial
connection, these fastenings must be removed. To do
so:
1 Loosen the central screws in the supports (painted
yellow) of the tandem compressors without re‐
moving them.
2 Remove the two fasteners -1-.
3 Tighten the central screws until the are completely
screwed in.
4 Check that the tandem compressors are resting
on their antivibration supports.
D A N G E R
All side panels except for that of the electrical box,
must be fitted, closed and secured with their cor‐
responding locks before turning the general switch
on the unit.
The unit has a remote control, which means that
the fan turbine may start unexpectedly.
C A U T I O N
Loose connection terminals produce overheating of
cables and terminals. The unit is working incorrectly
and there is a risk of fire.
Check that the cables are firmly secured to their con‐
nection terminals.
C A U T I O N
Do not turn on the general switch on the unit or start
the unit until all installation work has been completed.
Initial connection of the unit
Once all of the planned accessories are installed, and
before starting the unit, its general switch must be
turned on. -Q3-.
Press the "Test" button for two seconds so that the
unit recognises the installed accessories. When the
recognition process is complete, the red pilot light
switches off.
Rotating direction of the scroll compressors
Installation manual
Instructions for starting up the unit 1.16