Method Of Checking The Inverter's Power Transistors And Diode Modules; Diode Modules - Daikin CMSQ200A7W1B Service Manual

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

Method of Checking the Inverter's Power Transistors and Diode Modules

8. Method of Checking the Inverter's Power
Transistors and Diode Modules
8.1
Method of Checking the Inverter's Power Transistors
and Diode Modules
Checking failures in power semiconductors mounted on inverter PC board
Check the power semiconductors mounted on the inverter PC board by the use of a multiple
tester.
<Items to be prepared>
h
<Test points>
h
<Preparation>
h
Inverter PC board
Electronic circuit
h
h
h
h
In order to replace the faulty inverter, be sure to check for the points aforementioned.
250
Multiple tester : Prepare the analog type of multiple tester.
For the digital type of multiple tester, those with diode check function are
available for the checking.
Turn OFF the power supply. Then, after a lapse of 10 minutes or more, make measurement
of resistance.
To make measurement, disconnect all connectors and terminals.
J1
J2
J3
X10A
K2
J1
L1
J2
L2
L3
J3
According to the checking aforementioned, it is probed that the malfunction results from the
faulty inverter.The following section describes supposed causes of the faulty inverter.
Faulty compressor (ground leakage)
Faulty fan motor (ground leakage)
Entry of conductive foreign particles
Abnormal voltage (e.g. overvoltage, surge (thunder), or unbalanced voltage)
N3
U
P1
P3
P1
P2
P3
DM
N3
V
W
IGBT
U
V
W
X11A
SiBE28-805
Appendix