Daikin CMSQ200A7W1B Service Manual page 21

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

Specifications
ELECTRICAL SPECIFICATIONS
Name
Phase
Power Supply
Frequency
Voltage
Nominal Running
Current (RLA)
Minimum Ssc Value
Current
Minimum Circuit Amps (MCA)
Maximum Fuse Amps (MFA)
Total Overcurrent Amps (TOCA)
Full Load Amps (FLA)
Minimum
Voltage Range
Maximum
For Power Supply
Wiring Connections
For connection with
Indoor
Power Supply Intake
Notes
10
Hz
V
Cooling
A
Heating
A
kVa
A
A
A
A
V
V
Quantity
Remark
Quantity
Remark
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit
CMSQ200A7W1B
W1
3N~
50
400
9.53
8.38
11.9
16
15.6
0.4
360
440
5
Earth Wire Include
2
F1 - F2
Both Indoor and Outdoor Unit
circuit breaker)
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
temperature : 35°CDB
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
terminal is not below or above listed range limits
SiBE28-805
CMSQ250A7W1B
9.73
9.86
1,218
18.5
25
16.5
0.7
Specifications