E5" Outdoor Unit: Inverter Compressor Motor Lock - Daikin CMSQ200A7W1B Service Manual

Hide thumbs Also See for CMSQ200A7W1B:
Table of Contents

Advertisement

SiBE28-805
E5
3.16 "
" Outdoor Unit: Inverter Compressor Motor Lock
E5
Remote
Controller
Display
Applicable
CMSQ200A7, 250A7
Models
Method of
Inverter PC board takes the position signal from UVW line connected between the inverter and
compressor, and the malfunction is detected when any abnormality is observed in the phase-
Malfunction
current waveform.
Detection
Malfunction
This malfunction will be output when the inverter compressor motor does not start up even in
forced startup mode.
Decision
Conditions
Supposed
Causes
Troubleshooting
Inverter compressor lock
High differential pressure (0.5MPa or more)
Incorrect UVW wiring
Faulty inverter PC board
Stop valve is left in closed.
Troubleshooting by Indication on the Remote Controller
157