Fujitsu AG*G09LVCA Technical Manual page 26

Floor type
Hide thumbs Also See for AG*G09LVCA:
Table of Contents

Advertisement

CONTENTS OF FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote controller, in
accordance with the installed condition.
After turning on the power, perform the Function Setting by using the remote controller.
The settings may be selected between the following two: Function Number or Setting Value.
Settings will not be changed if invalid numbers or setting values are selected.
1)
2)
3)
4)
5)
6)
7)
8)
9)
Indoor unit fan control for energy saving for cooling
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Setting Description
Standard (400 hours)
Long interval (1,000 hours)
Short interval (200 hours)
No indication
2) Vertical airflow direction range control
In a concealed installation, change the setting to "Fixed" (02) to restrict the movement of the upper
air outlet so that the airflow is only towards the horizontal direction.
Setting Description
Standard
(Setting prohibited)
Fixed (Concealed)
3) Room temperature control for cooling
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
Setting Description
Standard
Slightly lower control
Lower control
Higher control
Filter sign
Vertical airflow direction range control
Room temperature control for cooling
Room temperature control for heating
Auto restart
Room temperature sensor switching
Remote controller signal code
External input control
Function Number
11
Function Number
23
Function Number
30
(  . . .Factory setting)
Setting Value
00
01
02
03
(  . . .Factory setting)
Setting Value
00
01
02
(  . . .Factory setting)
Setting Value
00
01
02
03
- (01 - 23) -