Siemens RDG400 Basic Manual page 41

With display, for vav
Hide thumbs Also See for RDG400:
Table of Contents

Advertisement

Environmental
conditions
Standards
General
Siemens
Building Technologies
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C (77 °F)
Temperature calibration range
Settings and display resolution
Setpoints
Current temperature value displayed
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Storage
Climatic conditions
Temperature
Humidity
EU Conformity (CE)
RCM conformity
UL
Electronic control type
Safety class
Pollution class
Degree of protection of housing
Connection terminals
Housing front color
Weight
*)
The documents can be downloaded from http://siemens.com/bt/download.
RDG400 Basic Documentation
0...49 °C (32...120 °F)
< ± 0.5 K (± 1 °F)
± 3.0 K (± 6 °F)
0.5 °C (1 °F)
0.5 °C (1 °F)
As per IEC 60721-3-3
Class 3K5
0...50 °C (32...120 °F)
< 95% r.h.
As per IEC 60721-3-2
Class 2K3
-25...60 °C (-13...140 °F)
< 95% r.h.
Class 2M2
As per IEC 60721-3-1
Class 1K3
-25...60 °C (-13...140 °F)
< 95% r.h.
*)
CE1T3181xx
*)
CE1T3181en_C1
UL 916 PAZX
CSA-C22.2 No. 205 PAZX7
http://database.ul.com
2.B (micro-disconnection on
operation)
III as per EN 60730
Normal
IP30 as per EN 60529
Solid wires or prepared
stranded wires
2
1 x 0.4...2.5 mm
(14 gauge)
2
or 2 x 0.4...1.5 mm
(16 gauge)
RAL 9003 white
0.350 kg
CE1P3182en
2015-05-20
41/44

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents