4.7

Control sequences

4.7.1

Applications and sequences

Application VAV
Single-duct
Single-duct & electric heater
Single-duct & radiator
Single-duct with heat/cool coil
4.7.2

Sequences overview (setting via parameter P01)

The sequence can be set via parameter P01, if available.
The thermostats can be used in systems featuring:
· Heating only (P01 = 0)
· Cooling only (P01 = 1)
· Manual heating/cooling changeover (P01 = 2)
· Automatic heating/cooling changeover (P01 = 3)
· Heating and cooling mode (e.g. 4-pipe system) (P01 = 4)
The available modes depend on the application
(selected via DIP switches, see section 4.5).
Parameter
P01 = 0
Sequence
Mode
Heating mode
Available for:
ê
ü
Single-duct
3)
Single-duct &
electric heater
3)
Single-duct &
radiator
ü
Single-duct with
heat/cool coil
1)
Changeover air
2)
Changeover water; heating/cooling coil
3)
The thermostat operates in heating AND cooling mode. P01 is not available
RDG400 Basic Documentation
Sequences
h ( \ ), c ( / )
el.h + c ( 7\ / )
rad + c ( r\ / ),
h + c ( \ / )
P01 = 1
P01 = 2
Manually select
Cooling mode
heating or cooling
mode
ü
ü
3)
3)
ü
ü
P01 = 3
Automatic
heating/cooling
changeover via
external water
temperature
sensor or remote
switch
1)
1)
ü
3)
3)
3)
3)
2)
2)
ü
CE1P3182en