4.12.2 Parameters Of The "Expert Level - Siemens RDG400 Basic Manual

With display, for vav
Hide thumbs Also See for RDG400:
Table of Contents

Advertisement

Name
Expert level
P30
P-band/switching differential in heating mode
P31
P-band/switching differential in cooling mode
P32
P-band/switching differential for radiator
P33
Dead zone in Comfort mode
P34
Setpoint differential (w
)
D
P35
Integral action time
P36
Heating/cooling changeover cooling (X1/X2)
P37
Heating/cooling changeover heating (X1/X2)
P38
Functionality of X1
P39
Operating action of X1 if digital input
P40
Functionality of X2
P41
Operating action of X2 if digital input
P42
Functionality of D1
P43
Operating action of D1 if digital input
P44
Running time of Y1/Y2 output
(only with modulating PI control)
P46
Output Y1/Y2 (if not parameterized as 3-pos.)
P47
Control output for VAV/CAV
P51
Floor heating limit temperature
P54
Fan overrun time
(only when electric heater is used)
P63
Minimum output limitation air flow signal
P64
Maximum output limitation air flow signal
P65
Protection heating setpoint
P66
Protection cooling setpoint
P68
Extension Comfort period
P69
Temporary setpoint Comfort mode
(see also Comfort setpoint P08)
P71
Reload factory settings
ü
Parameter available
Note:
Siemens
Building Technologies

4.12.2 Parameters of the "Expert level"

P46: Setting to 2-position or 3-position is done with DIP 4
RDG400 Basic Documentation
Factory setting
Range
2 K (4 °F)
0.5...6 K (1...12 °F)
1 K (2 °F)
0.5...6 K (1...12 °F)
2 K (4 °F)
0.5...6 K (1...12 °F)
2 K (4 °F)
0.5...5 K (1...10 °F)
2 K (4 °F)
0.5...5 K (1...10 °F)
5 min
0...10 min
16 °C (61 °F)
10...25 °C (50...77 °F)
28 °C (82 °F)
27...40 °C (81...104 °F)
1 = external sensor
0 = --- (no function)
1 = room temp ext/ret air temp (AI)
2 = H/C changeover (AI/DI)
3 = operating mode contact [DI)
4 = dew point sensor (DI)
5 = enable electric heater (DI)
6 = fault input (DI)
0 (NO)
0 = = normally open/open
1 = normally closed/closed
2 = H/C changeover
0 = --- (no function)
1 = room temp ext/ret air temp (AI)
2 = H/C changeover (AI/DI)
3 = operating mode contact [DI)
4 = dew point sensor. (DI)
5 = enable electric heater (DI)
6 = fault input (DI)
0 (NO)
0 = = normally open/open
1 = normally closed/closed
3 = operating mode
0 = --- (no function)
changeover
2 = H/C changeover (DI)
3 = operating mode contact [DI)
4 = dew point sensor (DI)
5 = enable electric heater (DI)
6 = fault input (DI)
0 (NO)
0 = = normally open/open
1 = normally closed/closed
150 s
20...300 s
1 (On/Off)
1 = 2-position
2 = PWM
0 = 0...10 V
0 = 0...10 V
1 = 3-position
OFF
OFF, 10...50 °C (50...122 °F)
60 s
0...360 s
0%
0...P64 (%)
100%
P63...100 (%)
8 °C (46 °F)
OFF, 5 °C (41 °F)...W Cool Prot;
(W Cool Prot = 40 °C (104 °F) max.)
OFF
OFF, W Heat Prot...40 °C (104 °F);
(W Heat Prot = 5 °C (41 °F) min.)
OFF
OFF; 15...360 min
OFF
OFF = disabled
ON = enabled
OFF
OFF = disabled
ON = reload start
ü
ü
ü
ü
ü
ü
ü
ü
ü
0..6
ü
ü
0..6
ü
ü
0..6
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
31/44
CE1P3182en