Engineering; Connection Terminals - Siemens RDG400 Basic Manual

With display, for vav
Hide thumbs Also See for RDG400:
Table of Contents

Advertisement

G
X1
M
X2
G0
Siemens
Building Technologies
6

Engineering

6.1

Connection terminals

D1
GND
SELV
RDG400 Basic Documentation
G, G0
Operating voltage AC 24 V
Y10/G0
Control output for DC 0...10 V actuator
Y1/G, Y2/G Control output for On/Off, PWM or 3-position actuators
X1, X2
Multifunctional input for temperature sensor (e.g. QAH11.1)
or potential-free switch
Factory setting:
- X1 = external room temperature sensor
- X2 = sensor or switch for automatic heating/
Change of setting: Parameters P38, P40
M
Measuring neutral for sensor and switch
D1, GND
Multifunctional input for potential-free switch.
Factory setting: Operating mode switchover contact
Change of setting: Parameter P42
cooling changeover
37/44
CE1P3182en
2015-05-20