4.7.3
Control outputs configuration
(setting via DIP 4/5 and parameters P46/P47)
Application
ê
Single-duct
Single-duct and electric heater
Single-duct and radiator/floor heating
Single-duct heating/cooling coil
The function of the control outputs is set via DIP switches 4 and 5:
ON
ON
OFF
OFF
1
2
3
4
5
DIP 4:
Y10 =
DC 0...10 V
DIP 5: Y1/Y2 =
2-position
Y1, Y2:
If 2-position is selected, the factory setting is On/Off.
If you want PWM (pulse width modulation), set parameter P46 to 2 = PWM.
P47:
· 0 = VAV box DC 0...10 V control signal
· 1 = VAV box: 3-position control signal
For details concerning connection of peripheral devices and setting of the DIP
switches, refer to Mounting Instructions M3182 [3].
RDG400 Basic Documentation
Control outputs
ü
ü
ü
ON
OFF
1
2
3
4
5
1
2
DC 0...10 V
3-position
ü
ü
ü
ü
ü
ü
ü
ON
OFF
3
4
5
1
2
3
DC 10...0 V
DC 10...0 V
(inverted)
(inverted)
2-position
3-position
CE1P3182en
2015-05-20
ü
ü
ü
ü
4
5
19/44