Daikin R22 Installation Manual page 9

Hide thumbs Also See for R22:
Table of Contents

Advertisement

Ceiling Concealed Drain Piping Work
The drain pipe must be installed as shown in the diagram (see diagram above) to avoid damage caused by leaks and
condensation.
For the best result, keep the piping as short as possible. Slant the piping at an angle to improve the Á ow.
Ensure the drain pipe is securely insulated.
It is necessary to provide a drain trap in the drain outlet to relieve pressure that exists within the unit compared to the outside
atmospheric pressure when the unit is operating. The drain trap is to avoid possibility of splashes or an odor.
Keep pipes as straight as possible for easy cleaning and to prevent the accumulation of dirt and debris.
Conduct a water drainage test after the installation is completed. Make sure that the drainage Á ow is smooth.
In humid environments, use an extra drain pan to cover the entire area of the indoor unit.
Unit : mm

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents