FDM50JEV1K - RD50JEY1K
FDM60JEV1K - RD60JEY1K
COMP
L
Indoor unit
Terminal Block
N
Model
Voltage range**
Power supply cable size*
Number of conductors
Interconnection cable size*
Number of conductors
Recommended time delay fuse*
Interconnection cable
Power Supply Cable
Indoor
Outdoor
Indoor
Outdoor
mm
2
2
mm
A
COMP
Outdoor unit
Terminal Block
L
N
R
S
T
N
!
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
FDM50JEV1K
RD50JEY1K
220-240V/1Ph/50Hz+!
308-415V/3N~/50Hz+!
2.5
5
2.5
4
16
FDM60JEV1K
RD60JEY1K
2.5
5
2.5
4
20