General Specifications - Omega Engineering RH/Temperature Transmitter HX93A User Manual

Rh/temperature transmitter
Table of Contents

Advertisement

16. Maintenance
If your Humidity transmitter will be used in a dusty environment, the
protective sensor filter, if clogged, may be removed for cleaning.
Unscrew the protective cover and gently blow compressed air through
the filter screen. A soft brush may also be used to remove dirt particles
from the screen.
If the sensor is subjected to 100% condensation, it must be dried to
obtain correct readings. There will be no permanent damage or
calibration shift to the unit.
Units should not be exposed to high concentrations of ammonia or
alcohol vapors.
17. Specifications
Relative Humidity
Measuring Range:
Accuracy:
Repeatability:
Operating
Temperature Range:
Output:
Model: HX93AC
Model : HX93AV
Power:
Max Loop Resistance:
RH Time Constant (90%
response at 25ºC, in
moving air at 1m/s):
Sensor Type:
Temperature
Measuring Range:
Accuracy:
Repeatability:
Output:
Model: HX93AC
Model : HX93AV
Power:
No Displays
With Displays
HX93A, HX93DA SERIES
RH/Temperature Transmitter
3 - 95% (non-condensing)
±2.5% @ 72ºF with an added temperature
coefficient error of -.06% RH/ºF (both
increasing and decreasing in temperature).
± 1 % RH
-20 to 75ºC (-4 to 167ºF)
4 to 20 mA (Scaled for 0 to 100% RH)
0 to 1 Vdc (Scaled for 0 to 100% RH)
6 –30 Vdc @ 20mA
Ohms = (V supply – 6 V)/.02 A
>10 seconds, 10 to 90% RH
>15 seconds, 90 to 10% RH
Thin Film Polymer Capacitor
-20 to 75ºC (-4 to 167ºF)
± 0.6ºC (1ºF)
± 0.3ºC (0.5ºF)
4 to 20 mA (Scaled for 0 to 100% RH)
0 to 1 Vdc (Scaled for 0 to 100% RH)
6 -30 Vdc @ 20mA
12 - 30 Vdc @ 30mA