11. Calibration

Your transmitter has been factory calibrated to meet or exceed the
specifications outlined in this manual. To maintain original
specifications it is generally recommended that your transmitter be re-
calibrated on an annual basis depending on operating conditions.
12. Calibration Procedure for HX93AC (all styles)

Relative Humidity Adjustment

Recommended equipment:
• Humidity Calibration Kit, OMEGA
• Handheld Digital Multi-meter, OMEGA
• Dc Power Supply, OMEGA
1. Remove enclosure cover
2. Connect transmitter as shown in figure below.
3. Apply power to transmitter and allow to warm up for 15 min.
4. Place unit in a 11% RH environment and allow to stabilize for 15 min.
5. Adjust potentiometer "P1" for a output reading of 5.76 mA
6. Place unit in a 75% RH environment and allow to stabilize for 15 min.
7. Adjust potentiometer "P2" for a output reading of 16.0 mA
8. Repeat steps 4, 5, 6, and 7 as necessary until proper readings are maintained.
9. Calibration complete.