The following information displays the current settings and states on the LPB/BSB
bus.
Path: Home > 0.5 OZS164... > Device information > LPB / BSB
Data point
Connected bus
Segment number
Device number
Clock time source*
Number of devices max
Number of devices
current
Last change
* This setting only works on the LPB. The clock time supplier is assigned
automatically on the BSB.
Web server
Operate using a web browser
Explanation, example
The web server autonomously identifies the bus
system connected. Possible values ---, LPB,
B
SB.
P art of the LPB device address.
P art of the LPB device address.
• Autonomous: Time/date is created from the
Quartz of the web server. No synchronization
with bus devices.
• Slave with remote setting: Web server
receives time/date from master. The master
supplies both date and time on the web
server and is then sent to all bus devices.
• Slave without rem setting: Web server
receives time/date from master. The web
server date/time setting is not sent to the
master. The master resets date/time.
• Master: Time/date is created from the Quartz
of the web server. The web server supplies
both date and time to all bus devices.
Recommended: Configure the web server as
Master and the bus device as slave with or
w
ithout remote setting.
Maximum possible number of devices monitored
b
y the web server on the LPB/BSB bus.
Actual number of devices monitored by the web
s
erver on the LPB/BSB bus.
T ime of last change to device list.
53 / 108
CE1C5711en
25.08.2010