LPB and BSB plants
Web server
Commissioning instructions
CE1C5711en
CE1C5711en
25.08.2010
25.08.2010
OZS164...
Building Technologies
Building Technologies

Advertisement

Table of Contents
loading

Summary of Contents for Siemens OZS164 SERIES WEB SERVER

  • Page 1 LPB and BSB plants Web server Commissioning instructions OZS164… CE1C5711en CE1C5711en Building Technologies Building Technologies 25.08.2010 25.08.2010...
  • Page 2 Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 © 2010 Siemens Switzerland Ltd www.siemens.com/sbt Subject to change 2 / 108 Siemens Web server CE1C5711en Building Technologies...
  • Page 3: Table Of Contents

    Web server faults ..................58 File transfer .....................59 SMS operation ..................62 Overview ....................62 Plant operation ..................64 4.2.1 Login .......................64 4.2.2 Query data ....................65 4.2.3 Change data....................67 4.2.4 Log off .....................67 3 / 108 Siemens Web server CE1C5711en Building Technologies Table of contents 25.08.2010...
  • Page 4 6.3.1 Internet protocol ..................88 6.3.2 Free e-mail account providers..............88 6.3.3 Install RNDIS driver.................89 6.3.4 Alternative network configuration............92 6.3.5 Siemens routers ..................93 Technical data ..................94 6.4.1 Web browser / OS ...................94 6.4.2 Web server ....................94 6.4.3 Connection terminals ................96 6.4.4 Pin assignments ..................96 6.4.5...
  • Page 5: Overview

    Do not open the device. Failure to comply will invalidate any warranty claims. The technical data are provided solely for use with Siemens bus devices. Users ensure the functionality of operation when using third-party devices not expressly mentioned here. Siemens does not provide service or guarantee services in this case.
  • Page 6: Display And Operating Elements

    History data is not deleted Switches • Position "On" Message Messages cannot be sent • Position "Off" Messages can be sent suppression (DIP switches) No function 6 / 108 Siemens Web server CE1C5711en Building Technologies Overview 25.08.2010...
  • Page 7: Web Operation

    • Click the field to go directly to the display of all plant faults. 6 Plant name Shows the web server name. Shows the contents of the selected function. 7 Display Shows Logo 1 and Logo 2. 8 Logo area 7 / 108 Siemens Web server CE1C5711en Building Technologies Overview 25.08.2010...
  • Page 8 • Administer own user account • Operate service and end user data Administrator • Fault overview • Documents, Message history, Logos and System definitions • Administer all user accounts • Create device websites 8 / 108 Siemens Web server CE1C5711en Building Technologies Overview 25.08.2010...
  • Page 9: Symbols, Notations, Abbreviations

    File upload (to web server) File download (from web server) Safety note, intended to protect against misuse Always observe/follow Note; important information Network connection Link to device User Message history System definitions Logos 9 / 108 Siemens Web server CE1C5711en Building Technologies Overview 25.08.2010...
  • Page 10: Notations

    • PC: Start > Settings > Network connections > Local Area Connection IP address, domains Entry in the web browser address line: • IP address: 192.168.2.10 • Domain: www.siemens.com Buttons Buttons are depicted as follows: 1.4.3 Abbreviations Abbreviations Auto MDI-X...
  • Page 11: Commissioning

    • Recommended by clock time supplier: The LPB bus device is clock slave with remote setting. • IP address USB: Notes 192.168.250.1 (unchangeable) • IP address Ethernet: 192.168.251.1 (ex works) 11 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 12: Getting Started

    4. The RNDIS driver is installed automatically if the PC is connected to the Internet and no RNDIS driver is installed. The installation wizard will guide you through installation. Note You can also manually set up the RNDIS driver (see Section 6.3.3). 12 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 13: Log Into Web Server

    • When you log in for the first time, you must enter "User name" = "Administrator", Notes "Password" = "Password". • Change the password after initial login. • Note case sensitivity. • English is the web browser language after the initial login. 13 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 14: Administer User Accounts

    Enter / select user data: - User name - Password - Repeat password - Description (optional) - E-mail address (optional) - Language: English - User group. Click to finish. 14 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 15 • A secure password is comprised of lowercase and uppercase letters, numbers and special characters, is at least 20 characters long, and does not include a name or words from dictionaries. 15 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 16: Create Device Web

    The workflow below shows how to add a bus device and create the associated evice web page(s): Click Enter the bus address: LPB: Segment number and Device number. BSB: Device number (default: 1=basic device). 16 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 17 : This process may take a few minutes. Wait until the message " Process finished" appears. In the device list, the web server and the bus device display status "Generated". Click to finish. 17 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 18 The web server removes the device from the device list. Wait until the message " Process finished" appears. Click to confirm. The device is removed from the device list. 18 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 19 : This process may take a few minutes. Wait until the message " Process finished" appears. Click to finish. In the device list, the web server and the bus device display status "Generated". 19 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 20 The device web pages are updated. Note : This process may take a few minutes. Wait until the message " Process finished" appears. The device list for the web server display status "Generated". 20 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 21: Web Server Settings

    • Otherwise, both date and time must be newly set. Data point Explanation, example T ime of day/date Set the current time and date. he weekday is calculated automatically. Default val.: 00:00 1.1.2005 Setting val.: Time of day/date 21 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 22: Operating Page Settings "Settings

    Web server language. — The language set is applied to web server Default val.: English Setting val.: See example fault text messages, message history, messages and system reports, and SMS essages. 22 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 23 (daylight saving ime), i.e. time is adjusted backward one hour. Note Disable the function by setting both start of daylight saving and standard time to the same date. 23 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 24 * This setting only works on the LPB. The clock time supplier is assigned automatically on the BSB. 24 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 25 The web server registers its existence via Ethernet, when • "UPnP localization" = "Ethernet" is set and • The connection between PC/laptop and the web server is active via Ethernet. 25 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning...
  • Page 26 S ignature line 1..10 Signatures are transmitted with the e-mail. — They identify the sender, e.g. the plant's Default val.: (Blank) Setting val: Max. 46 nternet address. characters 26 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 27 The web server registers its existence in the USB network, when • "UPnP localization" = "USB" is set and • The connection between PC/laptop and the web server is active via USB. 27 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 28 (Unicode). A maximum of 70 characters can be transmitted per SMS. GSM-7: The protocol is fixed GSM-7-Bit. Up to 160 characters can be transmitted per text essage. The character set is limited. 28 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 29 S ession timeout Timeout during which SMS operation is — locked for other users. Default val.: 5 minutes Setting val: 1-30 minutes The Session timeout is restarted with each MS accepted. 29 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 30 Setting value is the recipient's phone number Default val.: (Blank) Setting val: Phone number (e.g. mobile phone) where messages (fault (Format: +<int. area code>…) and service messages, system reports) are ent. 30 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 31 : Setting Unlimited may result in high hone bills. T ime to next message For SMS recipient type: — Waiting time to next message. Default val.: Setting val: 0… 840 min (Resolution 1 min) 31 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 32 "Only urgent ones". N ext report Waiting time to next system report. — Default val.: (day) Setting val: 0...255 d (Resolution: 1 d) 32 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 33 Setting val: Max. 20 characters ater press too low. * Notes: • Note Section 2.4, Section "Update device web pages". • Delete the entry to reset to default text. 33 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 34 The setting Urgent sends the fault to all active Default val.: Urgent Setting val: Urgent message recipients. The setting Not urgent Not urgent exempts all message recipients subscribing to " Only urgent ones". 34 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 35 (start of fault). Default val.: Coming Setting val: Coming, Coming and going: A corresponding Coming and going message is triggered at start and end of fault. indicates a bus device fault. 35 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 36 This text is used in the device list. Default val.: (Blank) etting val: Max. 20 characters * Notes: • Note Section 2.4, Section "Update device web pages". • Delete the entry to reset to default text. 36 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 37: Operating Page Settings "Message Recipient

    00:00 On … day's status is transferred to the current day. Special day The default settings is to always send 00:00 On … messages. Setting val: Monday...Sunday, Special day 00:00…24:00 Off/On 37 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 38 Holiday or special day can be selected as Reason. Beginning and End of the periods can be indicated Reason Annually with date and time. Selecting Annually repeats the eriods each year. 38 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 39 • Select checkbox Notes to select active entries. • Select "Annually" to set annually recurring switching times. • Click to check the data before it is saved. Check 39 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 40: Commission Network Components

    255.255.255.0 IP address: 192.168.2 .199 Subnet mask: 255.255.255.0 Default gateway: 192.168.2.1 Preferred DNS server: 192.168.2.1 OZS164... IP address: 192.168.2 Subnet mask: 255.255.255.0 Default gateway: 192.168.2.1 Preferred DNS server: 192.168.2.1 40 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 41: Operator Station On A Local Area Network (Lan)

    PC with web browser on a local area network (LAN): • IP address • Subnet mask Note The address es in the illustration are examples must be adapted to router addressing. See Section 5.1.1 for more details. 41 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 42: Router

    • DynDNS: The connection's dynamic IP address must be published if no static public IP address is available. Note Settings depend on network type and application. The different variants are described in Section 5.1.2. 42 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 43: Functional Check

    Display values: ---, Yes, No Yes: Message sent successfully. Message recipient not reached. M essage inhibition Shows the message suppression switch — etting (8) (see Section 1.2). Display values: Yes, no 43 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 44: Additional Settings

    Delete history of all events and messages. — Note : Setting value Yes is a temporary state, i.e. the Default val.: Setting val: alue automatically returns to No after ca. 2 seconds. 44 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 45: Final Steps

    – The web server sends a system report to the defined message recipients. – Fault LED (4) displays (flashing) error in establishing communications. LED On must be steady green. Fault LED must be dark. 45 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 46: Default State

    Note See Section 3.4 for information on uploading system definitions. Logo update The logos can be customized. Note See Section 3.4 for information on uploading logos. 46 / 108 Siemens Web server CE1C5711en Building Technologies Commissioning 25.08.2010...
  • Page 47: Operate Using A Web Browser

    • Password Note You can automate the process by adding the login information to the web browser’s address line. Format: <IP address>/main.app?user=<User name>&pwd=<Password> Example: 10.169.9.121/main.app?user=Administrator&pwd=Password 47 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 48: Plant Operation

    Click the left menu pane to select web server operation. The web server displays web server the top level of the menu tree. From here, you can go to all operating pages and data points. 48 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser...
  • Page 49 T ime of day/date Set the current time and date. T he weekday is calculated automatically. Default val.: 00:00 1.1.2005 etting val.: Time of day/date 49 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 50 Copy days • Click to check the data before it is saved. Check 50 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 51 • Select checkbox Notes to select active entries. • Select "Annual" to set repetitive switching points. • Click to check the data before it is saved. Check 51 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 52: Web Server Diagnostics

    F ield bus module 1 type Software version F ield bus module 1 software version Message inhibition Shows the setting of the message uppression switch (8) 52 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 53 T ime of last change to device list. * This setting only works on the LPB. The clock time supplier is assigned automatically on the BSB. 53 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser...
  • Page 54 An alternative DNS server is only defined for edundant systems and is typically empty. Physical address The physical address is a unique identification or the Ethernet interface. 54 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 55 • Ready: Normal status after successful network login. Phone number The setting value corresponds to the phone number provider assigned by the external telephone provider (e.g. wisscom) to send messages. 55 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 56 • Unknown • Roaming: Connected to SIM card issuer roaming partner network. Network operator S hows the network name where the modem is logged in. 56 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 57: Faults

    • Fault information (date, time, fault code). • Fault text • Device address • Device type • Click Note to go to the corresponding device's web operation. 57 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 58: Web Server Faults

    Displays for each fault: • Fault information (date, time, fault code). • Fault text Note See Section 6.2.1 for an overview of all web server faults. 58 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 59: File Transfer

    (messages.txt: Text file, messages.xls: Excel file). The "File download" dialog box opens. Open the file with the application or save it to any location. 59 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser...
  • Page 60 You must recreate the devices following a system definition upload. • System definition file transfer is available to administrator and service user Notes levels. • Uploading and installing may take more than 5 minutes. 60 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 61 • The left logo (Logo 1) has max. 625 x 54 pixels. • The right logo (Logo 2) has max. 200 x 54 pixels. • The original logos are restored when resetting the web server to default. 61 / 108 Siemens Web server CE1C5711en Building Technologies Operate using a web browser 25.08.2010...
  • Page 62: Sms Operation

    • SMS operation can be password-protected and limited to allowed phone numbers (see Section 2.5.2, "SMS operation"). • To prevent damage of the SIM card, only insert or remove the SIM card in powerless state of the device. 62 / 108 Siemens Web server CE1C5711en Building Technologies SMS operation...
  • Page 63 (see "User accounts" in primary navigation). The user language must be adapted to the web server language to get to the currently active data point texts for the web server. 63 / 108 Siemens Web server CE1C5711en Building Technologies SMS operation 25.08.2010...
  • Page 64: Plant Operation

    • After successful login, access to the plant is limited to the phone number dialing until the session times out or is terminated via logoff. • No confirmation is sent on wrong passwords to avoid costs associated with misuse. 64 / 108 Siemens Web server CE1C5711en Building Technologies SMS operation...
  • Page 65: Query Data

    < Data point text> Web server  Mobile phone Receive SMS: <Data point text>=<Value> <Data point text>=<Value> … < Data point text>=<Value> Note "<>" are not part of the entry. 65 / 108 Siemens Web server CE1C5711en Building Technologies SMS operation 25.08.2010...
  • Page 66 • Data can also be queried without login if no password is required. Access to the plant, however, is limited only to the sending phone number until the session times out or is terminated by logoff. 66 / 108 Siemens Web server CE1C5711en Building Technologies SMS operation 25.08.2010...
  • Page 67: Change Data

    Mobile phone  Web server Send SMS to plant phone number: Web server  Mobile phone N o feedback. You can also terminate the current session with "*" if no password is required. Note 67 / 108 Siemens Web server CE1C5711en Building Technologies SMS operation...
  • Page 68: Communication

    255.255.255.0 IP address: 192.168.2 .199 Subnet mask: 255.255.255.0 Default gateway: 192.168.2.1 Preferred DNS server: 192.168.2.1 OZS164... IP address: 192.168.2 Subnet mask: 255.255.255.0 Default gateway: 192.168.2.1 Preferred DNS server: 192.168.2.1 68 / 108 Siemens Web server CE1C5711en Building Technologies Communication 25.08.2010...
  • Page 69 • The web server IP address must be entered manually. The web server cannot be configured as DHCP client. • We recommend using IP addresses from the private range in the home network (see Section 6.3.1). 69 / 108 Siemens Web server CE1C5711en Building Technologies Communication...
  • Page 70 Select Start > Control Panel > Network Connections > Local Area Connection. Select the "General" tab. Click Properties Select "Internet Protocol (TCP/IP)". Click Properties Select “Use the following IP address”. 70 / 108 Siemens Web server CE1C5711en Building Technologies Communication 25.08.2010...
  • Page 71 • The default gateway and DNS server settings have no meaning for LANs without router, provided no e-mail is sent within the home network. • We recommend using IP addresses from the private range in the home network (see Section 6.3.1). 71 / 108 Siemens Web server CE1C5711en Building Technologies Communication...
  • Page 72: Remote Operation Via The Internet

    An appropriate connection is required (e.g. DSL router) for remote operation via Internet. Setting up Internet access is not described here. • The examples here were created using the Siemens Gigaset SX763 router (see Notes Section 6.3.5). Workflow, terms and functionality may differ when using other products.
  • Page 73 We recommend enabling the firewall to protect the local area network: Firewall • Firewall: On. Address Translation Activate NAT to ensure that the web server can be reached via the Internet. (NAT) • NAT: On. 73 / 108 Siemens Web server CE1C5711en Building Technologies Communication 25.08.2010...
  • Page 74 • We recommend using Forwarding Ports from the private range for the port (see Section 6.3.1). In the example, queries from the Internet to a public IP address (Internet connection)/Port 80 are forwarded to local IP address 192.168.2.10 (web server)/port 80. 74 / 108 Siemens Web server CE1C5711en Building Technologies Communication 25.08.2010...
  • Page 75 After setting up the account, DynDNS sends an e-mail with a link that must be queried within 48 hours. You then login with • User (user name from above). • Pass (password from above). 75 / 108 Siemens Web server CE1C5711en Building Technologies Communication...
  • Page 76 • Service Type: Select "Host with IP address" • IP Address: Current IP router address. Click "Use auto detect IP address …" to automatically assume. • Click Create Host 76 / 108 Siemens Web server CE1C5711en Building Technologies Communication 25.08.2010...
  • Page 77 • Service provider: Service provider (DynDNS.org). • Domain name Domain = Host name (own name, e.g. myhome.dyndns.info). • User name: User name for the DynDNS account (e.g. MyUserAccount). • Password: Password for DynDNS account. 77 / 108 Siemens Web server CE1C5711en Building Technologies Communication 25.08.2010...
  • Page 78: Messages Via E-Mail

    SMTP is used to send fault messages and system reports via e-mail. The mail server (SMTP server, outgoing mail server) must be known to the web server to send e-mails to the recipients. Email address of sender Email address receiver e.g. myaccount@bluewin.ch e.g.service@siemens.com Internet DSL-Router DSL-Router DNS-Server Mailserver Ethernet mail.bluewin.ch...
  • Page 79 Fault web server E-mail example Datapoint, Information From: myhome@bluewin.ch … > Communication > E-mail: E-mail address sender service@siemens.com … > Message receiver > Message receiver 1…4: E-mail address Subject: Message central comm unit: Message type: Demo HCS, …> Texts: Name,...
  • Page 80 Fault input 1..2 E-mail example Datapoint, Information From: myhome@bluewin.ch … > Communication > E-mail: E-mail address sender service@siemens.com … > Message receiver > Message receiver 1…4: E-mail address Subject: Message central comm unit: Message type: Demo HCS, …> Texts: Name, …>...
  • Page 81 Systemreport with fault E-mail example Datapoint, Information From: myhome@bluewin.ch … > Communication > E-mail: E-mail address sender service@siemens.com … > Message receiver > Message receiver 1…4: E-mail address Subject: System report central comm unit: Message type: Demo HCS, N OK >...
  • Page 82 "User name" and "Password" from the mail server for each e- mail transmission. • The mail server can also be installed on the local area network. 82 / 108 Siemens Web server CE1C5711en Building Technologies Communication...
  • Page 83: Messages Using Sms (Gsm)

    Number of messages for sending Number of messages to be sent from the — essage buffer. Current repetition interval Current interval until next sending — ttempt. SMS message example: 83 / 108 Siemens Web server CE1C5711en Building Technologies Communication 25.08.2010...
  • Page 84 System report SMS message example Datapoint, Information 15.09.2009 08:45 +41417241000 Date, time, phone number 15.09.2009; 08:44 Time of occurrence Demo HCS, N. OK / OK …> Texts: Name, State 84 / 108 Siemens Web server CE1C5711en Building Technologies Communication 25.08.2010...
  • Page 85: Appendix

    1B28 Γ 1B40 Δ 1B29 Θ 1B3D Λ 1B3C <ESC> Ξ 1B2F ¡ Π 1B3E £ Σ 1B14 ¤ Φ < ¥ Ψ § Ω > ¿ € 1B65 85 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 86: Diagnostics

    - Receiver type SMS: Incorrect phone number receiver or SMS service provider, empty prepaid SIM card, problems receiving or connecting on the GSM network - Receiver type E-mail: Faulty Ethernet or E-mail settings 86 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 87: Windows Commander

    Checks whether DNS and mail servers can be reached. nslookup <IP address> Translates an IP address to the domain name and vice r <domain> versa: Look up domain names. 87 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 88: Communication

    Only with NetCologne DSL connection T-Online mailto.t-online.de Only with T-Online DSL connection T-Online smtpmail.t-online.de Tiscali smtp.tiscali.de Only with Tiscali DSL connection Additional information on free e-mail providers: • http://www.patshaping.de/hilfen_ta/pop3_smtp.htm • http://www.iopus.com/guides/bestpopsmtp.htm 88 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 89: Install Rndis Driver

    Confirm hardware installation: Click Continue installation Wait until installation is complete and click Finish Result: The RNDIS driver is now installed. The PC can communicate with the web server via USB. 89 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 90 • The RNDIS driver is supplied on the web server at http://<IP address>/drivers/ You can copy the file "SBT_RNDIS.zip" to your PC via the Ethernet connection (see Section 2.6.1) and unzip it. 90 / 108 Siemens Web server CE1C5711en Building Technologies Appendix...
  • Page 91 • The RNDIS driver is installed as part of the ACS700 Siemens software installation. 91 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 92: Alternative Network Configuration

    Enter IP address, subnet mark and operational standard gateway as well as DNS server. Result: The PC assumes the configuration with these settings as soon as it is no longer integrated in the default network. 92 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 93: Siemens Routers

    6.3.5 Siemens routers We recommend the following router from Siemens to connect to an internal network with DSL connection: We recommend the Gigaset SX763 WLAN dsl by Siemens. This router supports all requirements for troublefree operation of a web server.
  • Page 94: Technical Data

    Max. 100 m Digital inputs Interface type Protective low voltage for potential-free low voltage-capable contacts Voltage at open contact DC (16…19) V Current at closed contact DC (4...6) mA 94 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 95 OZS164.23 Full unit 0.143 kg Complete device (basic unit with packaging, installation 0.601 kg instructions, power supply unit, USB and Ethernet cable, cable ties) Packaging Cardboard box 95 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 96: Connection Terminals

    Rx – Rx + Unassigned Unassigned Unassigned USB plug T ype Mini-B D – Terminal assignment A LPB/BSB connections DB/CL+ DB/CL+ MB/CL– MB/CL– Digital inputs T erminal assignment C 96 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 97: Connection Diagram

    DC 24 V D2 M D2 M DB/CL+ DB/CL+ MB/CL- MB/CL- Web server LPB/BSB device P1, P2 Devices with potential-free contact output for fault indication 6.4.6 Dimensions 87.5 Drilling plan 97 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 98 39.2 OZS164.13 87.5 39.2 OZS164.23 87.5 98 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 99: Glossary Of Ethernet And Internet Terms

    Domain name The domain name is the web server designation on the Internet. The DNS server assigns an IP address to the domain name. Domain Name System See DNS 99 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 100 (e.g. the Internet). Gateway A gateway is a device connecting networks of different architecture (addressing, protocols, interfaces, etc.). Although not entirely correct, the term often is used interchangeably with router. 100 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 101 In LANs, data is exchanged and resources are used jointly. A LAN can be connected to other networks such as WAN or Internet. Local Area Network See LAN 101 / 108 Siemens Web server CE1C5711en Building Technologies Appendix...
  • Page 102 (web server) integrated in a LAN, can be reached from the Internet (without a need for a public IP address). Port Forwarding is achieved by the correct NAT / PAT definition in the router. 102 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 103 SMTP The SMTP protocol is a TCP/IP protocol. It controls e-mail traffic on the Internet. The ISP provides the SMTP server (mail server). Outdated form for TSL; see TSL. 103 / 108 Siemens Web server CE1C5711en Building Technologies Appendix 25.08.2010...
  • Page 104 (application). UDP, in contrast to TCP, is an unsecured protocol. UCP is a so-called connection-less protocol. Data packets are broadcast. The recipient is responsible for receiving data. The sender does not receive notification if the data packages were received. 104 / 108 Siemens Web server CE1C5711en Building Technologies Appendix...
  • Page 105 In addition, they automatically provide, depending on class, own services or use services of other devices on the network. A URL refers to an information source, e.g. http://www.siemens.com. The URL is a uniform web address that is used to determine the network protocol used (e.g. http) or the location of the resource on the network.
  • Page 106: Index

    Free e-mail account providers ......88 E-mail address sender ........26 Mail server address ........26 Mail server port number ........ 26 Glossary..............99 Ethernet IP address ............. 25 Subnet mask..........25 106 / 108 Siemens Web server CE1C5711en Building Technologies Index 25.08.2010...
  • Page 107 Time zone ............23 UPnP localization........... 27 Web operation Web server User interface............7 Language............22 Web server diagnostics .........52 Web server faults ..........58 Change data............67 Web server operation ..........48 Login..............64 107 / 108 Siemens Web server CE1C5711en Building Technologies Index 25.08.2010...
  • Page 108 Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 © 2010 Siemens Switzerland Ltd www.siemens.com/sbt Subject to change 108 / 108 Siemens Web server CE1C5711en Building Technologies...