Siemens OZS164 SERIES WEB SERVER Commissioning Instructions page 34

Table of Contents

Advertisement

Web server
Fault input 1...2
34 / 108
Siemens
Building Technologies
Path: Home > 0.5 OZS164... > Settings > Faults > Local > Web server
Data point
M essage triggering
Default val.:
Coming
Setting val:
Coming,
Coming and going
Path: Home > 0.5 OZS164... > Settings > Faults > Local > Fault input 1...2
The following settings specify behavior in case of faults.
Select "Settings > Inputs > Fault input 1...2" to configure the fault inputs.
Data point
F ault input 1..2*
Default val.:
(Blank)
Setting val:
Max. 20 characters
Fault status message
d
elay
mm:ss
Default val.:
00:05.
Setting val:
00:00...59:55
(Resolution 00:05)
F ault priority
Default val.:
Urgent
Setting val:
Urgent
Not urgent
Web server
Commissioning
Explanation, example
Coming: A message is triggered when a fault
is received (start of fault).
Coming and going: A corresponding
message is triggered at start and end of fault.
A
web server fault displays the LED
Explanation, example
Customizable text for fault input. The
designation is displayed in the menu and
transmitted as part of the message.
Identical to data point in "Settings > Inputs >
F
ault input 1...2".
The Fault status message delay acts as a
filter for short-term fault events. The time the
web server must wait until a fault becomes
a
ctive is set here.
Filter when sending a fault.
The setting Urgent sends the fault to all active
message recipients. The setting Not urgent
exempts all message recipients subscribing to
"
Only urgent ones".
.
CE1C5711en
25.08.2010