2.5 Connecting Power Cables

The I/O cables, battery cables and 10A charger cables (optional) are required for connection. When connecting the
cables, you should follow the local wiring regulations, take the environment situation into account, and refer to Table
3B of IEC60950-1.
The maximum current in different operating modes is listed in Table 2-2, the recommended minimum cable CSA is
listed in Table 2-3. Select the appropriate cables according to Table 2-2 and Table 2-3.
Model
10kVA (1-input 1-output)
10kVA (3-input 1-output)
Note:
When the battery cables are selected, according to the current value shown in this table, the max. allowable voltage drop is 4Vdc.
Do not ring the cables to avoid increasing the electromagnetic interference.
1: The input mains current of the rectifier and the bypass.
2: Non-linear load (switch mode power) affects the neutral cable design of the output and the bypass. The neutral cable current
may exceed the rated phase current, up to1.732 times as large as the rated current
Model
10kVA (1-input 1-output)
10kVA (3-input 1-output)
The recommended I/O MCB capability of the UPS is listed in Table 2-4. Select the MCBs according to your
requirements.
Model
10kVA (1-input 1-output)
10kVA (3-input 1-output)
UPS
Figure 2-13 Installing UPS with battery modules
Table 2-2 Max. steady state AC and DC current
1
2
Mains input current
upon battery
charging with max. ability
220V
230V
55
55
19
19
Table 2-3 Single UPS cable CSA (unit: mm
Input
10
10
Table 2-4 UPS I/O MCB selection
Recommended
Input interface
capability of input
external MCB
Terminal block
Terminal block
Liebert
ITA 10kVA UPS User Manual
®
Chapter 2 Single UPS Installation And Commissioning
Rated current (A)
Total output current
240V
220V
230V
55
46
44
19
46
44
2
, ambient temperature: 25° C
Output
Neutral cable
10
10
10
10
Battery MCB
125A
DC63A
125A
DC63A
2
at full load
Battery discharging current
upon min. battery voltage
240V
64
42
42
64
PE
10
10
Recommended
Output interface
capability of output
external MCB
Terminal block
Terminal block
15
Battery
16
16
70A
70A